Title |
Numerical Performance Analysis of the Swing Compressor |
Authors |
문석환(Seok Hwan Moon) ; 노기율(Ki Youl Noh) ; 사범동(Bum Dong Sa) ; 양장식(Jang Sik Yang) ; 최경민(Gyung Min Choi) ; 김덕줄(Duck Jool Kim) |
DOI |
http://dx.doi.org/10.6110 /KJACR.2012.24.1.077 |
Keywords |
스윙 압축기 ; 베인-롤러 일체형 ; 냉방능력 ; 압축기 일 ; 에너지 효율 비 Swing compressor ; Vane-roller integral type ; Cooling capacity ; Compressor work ; EER |
Abstract |
Numerical performance analysis of the vane-roller integral type swing compressor was conducted. The swing compressor has been investigated for the highly efficient air conditioning system. Performance analysis results of the swing compressor were compared with those of a conventional rotary compressor. Mechanical and gas losses of a swing compressor were larger than those of a rotary compressor. However in case of mass flow rate from the discharge port, the swing compressor was about 6.68% higher than the rotary compressor. Hence the EER, the cooling capacity and the compressor work of the swing compressor were about 3.71%, 6.69% and 2.90% higher than the rotary compressor respectively. |