Mobile QR Code QR CODE : Korean Journal of Air-Conditioning and Refrigeration Engineering
Korean Journal of Air-Conditioning and Refrigeration Engineering

Korean Journal of Air-Conditioning and Refrigeration Engineering

ISO Journal TitleKorean J. Air-Cond. Refrig. Eng.
  • Open Access, Monthly
Open Access Monthly
  • ISSN : 1229-6422 (Print)
  • ISSN : 2465-7611 (Online)
Title Characteristic of Thermal Output of Thermally Activated Building System During the Heating Operation According to FDM Analysis
Authors 임재한(Jae-Han Lim) ; 송진희(Jin-Hee Song) ; 구보경(Bo-Kyoung Koo) ; 송승영(Seung-Yeong Song) ; 성윤복(Yoon-Bok Senog)
DOI http://dx.doi.org/10.6110 /KJACR.2012.24.3.218
Page pp.218-223
ISSN 1229-6422
Keywords 구체축열시스템 ; 방열량 ; 유한차분법 ; 공급온수온도 Thermally activated building System ; Thermal output ; Finite difference method ; Supply water temperature
Abstract This study is focused on the evaluation of thermal output of TABS (Thermally Activated Building System). The aim of this study is to evaluate TABS in terms of the temperature difference between heating medium supply temperature (Ts)and return temperature (Tr), thermal output and the surface temperature distribution according to the design flow rate and the design flow temperature. Through the transient heat transfer simulation using temperature calculation using Crank-Nicolson FDM using Physibel Voltra 6.0 W, the temperature difference between Ts and Tr, thermal output and the surface temperature distribution of specific TABS was calculated and evaluated. The results show that specific thermal output and temperature difference at 60°C of supply water temperature were about 162 W/m2, 13.6°C respectively