Title |
Comparison of the Performance of the VAV Dampers for the Circular Duct |
DOI |
http://dx.doi.org/10.6110/KJACR.2012.24.9.699 |
Keywords |
변풍량 ; 댐퍼 ; 개도 ; 블레이드 ; 벤튜리형 ; 오리피스블레이드 VAV ; Damper ; Opening degree ; Blade ; Venturi ; Orifice-blade ; |
Abstract |
The performance of the typical VAV dampers; blade type, venturi type and blade-orifice type, for the circular duct, is obtained by measuring the volume flow rate as a function of the opening degree. The performance features are discussed by comparing the volume flow rate of each damper. It is shown that the blade-orifice type damper, recently developed, is excellent in its linearity of the performance and that it is worse than the blade type but much better than the venturi type in its flow resistance. |