A Case Study on the Plumbing Pipe Burst of Floor Radiant Heating |
Authors |
정홍도(Hongdo Jung) ; 신용한(Younhan Shin) ; 박진관(Chenkwan Park) ; 정효민(Hyomin Jeong) ; 정한식(Hanshik Chung) |
DOI |
http://dx.doi.org/10.6110/KJACR.2012.24.10.745 |
Keywords |
온돌 ; 바닥복사난방 ; 온도조절기 ; 인장강도 Ondol ; Floor radiant heating ; Thermostat ; Tensile strength |
Abstract |
Heating pipes burst was occurred in the apartment complex that was applied floor radiant heating system. There were two opinions for the cause of the bursted heating pipes that was the flaw during construction and defects in the product and also there were conflicting among them. Officials analyzed it in order to investigate the cause of the rupture. Tensile test results showed different tensile strength between the lower part of heating pipe and the upper part of heating pipes. The lower tensile strength is maintained while the top was not secured. The reason why rupture heating pipes is that flow velocity isn’t secured and then the air get stagnant. Stagnant air makes hardening. It is caused rupturing. The proper flow rate was confirmed 0.166 m/sec after experiment. It isn’t make stagnant air inside heating pipes. |