Title |
An Analytical Study on the Prediction of Indoor Air Quality and the Reduction of Air Conditioning Load in Bio Safety Level 3 Laboratory |
Authors |
홍진관(Jin Kwan Hong) ; 박현진(Hyun Jin Park) |
DOI |
http://dx.doi.org/10.6110/KJACR.2012.24.11.813 |
Keywords |
생물안전 3등급 연구시설 ; 생물재해 시나리오 ; 공기환경 ; 에너지 소비량 ; 멀티죤 시뮬레이션 Bio safety level 3 lab.(BSL3 lab.) ; Biohazard scenario ; Indoor air environment ; Energy consumption ; Multizone simulation |
Abstract |
In this study, the multizone simulation for biosafety of BSL3 lab. and energy simulation are carried out simultaneously by using linked model of CONTAM and TRNSYS. In BSL3 lab., annual energy consumption is approximately five to ten times more than the magnitude of the office building. This is because required air change rate is extremely large and it is difficult to maintain room pressure difference efficiently. To maintain pressure difference between laboratory rooms through sealing condition of doors and proper airflow control is significant. In this study, to predict indoor environment of the BSL3 lab.(Influenza A research lab.), the multizone simulation for four kinds of biohazard scenario is also performed as part of risk assessment. Multizone and energy simulation results by using linked model show that these approaches are used as a tool for the energy efficient design and operation method for the safer BSL3 lab. facilities. |