Analyses of Energy Savings and Night Heating Performance of a Movable Thermal Insulation Shuttered Window |
Authors |
이장만(Jang-Man Lee) ; 조수(Soo Cho) ; 임상훈(Sang-Hoon Lim) ; 송규동(Kyoo-Dong Song) |
DOI |
http://dx.doi.org/10.6110/KJACR.2013.25.3.150 |
Keywords |
고효율에너지 ; 단열셔터 ; 열관류율 ; 난방부하 High energy efficiency ; Thermal insulation shutter ; Thermal transmittance ; Heating load |
Abstract |
Usually, a window tends to have a lower thermal performance, than that of an ordinary wall. This study analyzes the enhancement of thermal performance of a window, when a Thermal Insulation Shutter is installed. The analyses were conducted at the laboratory, and with a full-scale mockup house, and the U-factor and heating load were examined. The laboratory results show that the U-factor increased by approximately 28%, when a Thermal Insulation Shutter was installed. The temperature difference was about 5°C, and this shows that the Thermal Insulation Shutter enhances the thermal performance of the window, when installed. The mockup house was used to calculate the heating load; the heating load was reduced by more than 41%, and shows that the installation of a Thermal Insulation Shutter is an effective way to reduce heating energy consumption. |