Energy Consumption Analysis based on Filter Differential Pressure when Adopting an Air-side Economizer System for a Data Center |
Authors |
박성현(Seonghyun Park) ; 서장후(Janghoo Seo) ; 정용호(Yong-Ho Jung) ; 장현재(Hyun-Jae Chang) ; 황석호(Seok-Ho Hwang) |
DOI |
http://dx.doi.org/10.6110/KJACR.2013.25.7.371 |
Keywords |
데이터센터 ; 외기도입 냉방시스템 ; 필터 차압 ; TRNSYS Data center ; Air-side economizer system ; Filter differential pressure ; TRNSYS |
Abstract |
Recently, many studies related to reducing the energy consumption in data centers have been conducted. These studies have mainly focused on the air intake and exhaust system of a computer room air handling unit (CRAH) in the server room, diffuser type, suppression and discharge of the heat generated from the server, and the air-side economizer system. In this study, the energy consumption of the conventional central chilled water cooling system is compared with the energy consumption of the air-side economizer system. We also examined how changes of differential pressure by each filter have influenced energy consumption, using the power usage effectiveness (PUE). Results show that the PUE was improved, and energy consumption decreased, by applying the air-side economizer system. |