Title |
A Study on the Development of a Multi-Heat Supply Control Algorithm in a District Heating Apartment Building in Accordance with the Variation of Outdoor Air Temperature |
Authors |
변재기(Jae-Ki Byun) ; 윤성호(Sung-Ho Yun) ; 남기훈(Ki-Hoon Nam) ; 최영돈(Young-Don Choi) ; 신종근(Jong-Keun Shin) |
DOI |
http://dx.doi.org/10.6110/KJACR.2013.25.11.585 |
Keywords |
지역난방 ; 공동주택 ; 열분배 배관 ; 외기온도 ; 열손실 ; 난방부하 ; 열공급 ; 세대 District heating ; Apartment building ; Heating distribution pipeline ; Outdoor air temperature ; Heat loss ; Heating load ; Heat supply ; Household |
Abstract |
In this study, we developed a heat supply control algorithm that minimizes the heat loss in the heat distribution pipelines used for supplying heat energy to shared group housing. Controlling the temperature and flow rate of the hot water supplied to the heat exchanger for shared group housing enables us to develop a heat supply control technique that meets the heating load required by each household in a shared apartment building in accordance with changes in the outdoor air temperature, and that minimizes the heat loss occurring in the heat distribution pipeline. A one-year study in 2008 on a 1,473-household D-apartment building in Hwaseong, Gyeonggi-do, South Korea, compared the heat capacity used by each household, as well as the heat capacity supplied to the heat exchanger room of the apartment housing building, to calculate the amount of heat loss in the heat distribution pipeline. The results confirmed that 24.1% of the heat supplied was lost in the piping. |