Mobile QR Code QR CODE : Korean Journal of Air-Conditioning and Refrigeration Engineering
Korean Journal of Air-Conditioning and Refrigeration Engineering

Korean Journal of Air-Conditioning and Refrigeration Engineering

ISO Journal TitleKorean J. Air-Cond. Refrig. Eng.
  • Open Access, Monthly
Open Access Monthly
  • ISSN : 1229-6422 (Print)
  • ISSN : 2465-7611 (Online)
Title An Experimental Study on a Heat Pump with Dehumidification Function that Utilizes Underground Air Heat
Authors 고지운(Ji-Woon Ko) ; 박윤철(Youn Cheol Park) ; 고광수(Gwang-Soo Ko)
DOI http://dx.doi.org/10.6110/KJACR.2014.26.2.055
Page pp.55-60
ISSN 1229-6422
Keywords 지하 공기열 ; 열펌프 ; 제습 ; 다중응축기 ; 다중증발기 Underground air heat ; Heat pump ; Dehumidification ; Multi condenser ; Multi evaporator
Abstract The present study has been conducted to develope a heating system for a green house with heat from underground air at Jeju Island. The temperature of the air deposited in the underground is 16~18℃ throughout the year, and it also has a large amount of moisture. Therefore, the air could not directly used for the heating of a green house. In this study, a heat pump with dehumidification function has been developed, which consisted of three evaporators, where the moisture removal occurs, accompanied by temperature drop. The dropped temperature is recovered, while passing through a series condenser. The air temperature increased from 17℃ to 35 with a 2.1 kg/h of moisture removal rate. The developed system moisture removal performance shows 0.91 kg/kWh.