Title Analysis of the Charging and Discharging Performance of a New Wavy Cylindrical Shape Capsule
Authors 홍상우(Sang Woo Hong) ; 이용태(Yong Tae Lee) ; 정재동(Jae Dong Chung)
DOI http://dx.doi.org/10.6110/KJACR.2014.26.7.301
Page pp.301-307
ISSN 1229-6422
Keywords 축열성능 ; 방열성능 ; 상변화 물질엔탈피 방법 Charging performance ; Discharging performance ; PCM ; Enthalpy method
Abstract This paper presents a numerical study on the constrained melting of a phase change material inside various capsule containers, using water and HDPE (High Density Polyethylene) as a PCM and a capsule material, respectively. The computations are based on an iterative, finite-volume numerical procedure that incorporates a single-domain enthalpy formulation for simulation of the phase change phenomenon. Using the enthalpy method, various capsule configurations, such as a capsule from E company, an isochoric cylinder capsule, an equivalent diameter sphere capsule, and an isochoric sphere capsule, are used to investigate the effect of capsule configurations on the charging and discharging performance. A transient three-dimensional model is used for each case. The simulation results show that the capsule from E company results in a higher melting and solidification rate of the PCM, than the other capsule configurations considered in this research.