Title |
Performance Analysis of a Wet Air-Cycle Refrigeration System |
DOI |
http://dx.doi.org/10.6110/KJACR.2014.26.11.504 |
Keywords |
공기사이클 냉동 ; 성능계수 ; 습도비 ; 상대습도 ; 엔트로피 생성률 Air-cycle refrigeration ; COP ; Humidity ratio ; Relative humidity ; Entropy production rate |
Abstract |
The objective of this study is to theoretically analyze the performance of an open wet air-cycle refrigeration system, which nowadays is increasingly generating environmental concern. The temperature and relative humidity of the outside air are selected as the most important parameters. As the temperature and relative humidity of the outside air increase, the pressure ratio of the ACM compressor is determined to be nearly constant, the air temperature at the exit of the system increases, and the amount of condensed water, the cooling capacity, the COP, and the total entropy production rate increase overall. The effects of the effectiveness of the heat exchanger and the efficiency of the turbine on the performance are greater than that of the efficiency of the ACM compressor. Also, the performance of the wet air-cycle refrigeration system with two heat exchangers is enhanced, with a high COP and low total entropy production rate, compared to the system with a single heat exchanger. |