Title |
Analysis of the Performance Test Results of a Heat Pump for Closed Cooling Water Heat Recovery on a Combined Thermal Power Plant |
DOI |
http://dx.doi.org/10.6110/KJACR.2014.26.11.541 |
Keywords |
열회수 ; 기기냉각수 ; 복합화력발전소성능시험 Heat recovery ; Closed cooling water ; Combined thermal power plant ; Performance test |
Abstract |
The present study was conducted to determine whether ESCO Business is success or not. ESCO Business recovers the investment costs by the energy savings resulting from complementing existing energy facilities. The guaranteed parameters are Quantity of Heat Recovery, and Generator output drop. The results of the Performance Test show that the Quantity of Heat Recovery increased by 11.52 Gcal/h, and Generator output decreased by 0.234 MW, which satisfied the guarantee value. |