Mobile QR Code QR CODE : Korean Journal of Air-Conditioning and Refrigeration Engineering
Korean Journal of Air-Conditioning and Refrigeration Engineering

Korean Journal of Air-Conditioning and Refrigeration Engineering

ISO Journal TitleKorean J. Air-Cond. Refrig. Eng.
  • Open Access, Monthly
Open Access Monthly
  • ISSN : 1229-6422 (Print)
  • ISSN : 2465-7611 (Online)
Title A Study for Optimization the Ventilation Performance of the Computer Room
Authors Yong-il Kwon
DOI http://dx.doi.org/10.6110/KJACR.2015.27.2.057
Page pp.57-62
ISSN 1229-6422
Keywords 환기성능 ; 급기디퓨저 ; 실내공기질 ; 국소공기연령 Ventilation performance ; Supply diffuser ; IAQ ; Local mean age
Abstract The objective of the present study is to identify the ventilation problems and to suggest the optimal ventilation system to save energy and to improve IAQ in the computer rooms, which annually performs the cooling operation by the server with the highly thermal load. Numerical results on the temperature and local mean age are presented along with some of the discharge velocities. Results show many interesting aspects of airflow patterns affecting the ventilation performances, according to the discharge velocity of the supply diffuser installed in the bottom surfaces between the servers. As the results, 2.5 m/s of the optimal discharge velocity is needed in order to improve the ventilation performance.