Mobile QR Code QR CODE : Korean Journal of Air-Conditioning and Refrigeration Engineering
Korean Journal of Air-Conditioning and Refrigeration Engineering

Korean Journal of Air-Conditioning and Refrigeration Engineering

ISO Journal TitleKorean J. Air-Cond. Refrig. Eng.
  • Open Access, Monthly
Open Access Monthly
  • ISSN : 1229-6422 (Print)
  • ISSN : 2465-7611 (Online)
Title Night Purge Evaluation Using the RTS-SAREK in Office Buildings
Authors Dongshin Shin ; Sungkeun Park ; Youngsoo Park ; Jisu Park ; Jinyoung Lee
DOI http://dx.doi.org/10.6110/KJACR.2015.27.12.633
Page pp.633-638
ISSN 1229-6422
Keywords 나이트퍼지 ; 냉방부하 ; 사무용 건물 ; 복사시계열법 ; 부하해석프로그램 Night purge ; Cooling load ; Office building ; RTS method ; RTS-SAREK
Abstract This study evaluates the capacity of night purging in office buildings to reduce the cooling load. RTS-SAREK is used to estimate the performance of night purging on the steady state. To overcome steady state RTS program limitations, we added unsteady heat transfer equations. When the ACH (Air Change per Hour) increases, the wall temperature decreases in both the steady and unsteady states. The unsteady heat transfer rate is different from the steady transfer rate, which validates the unsteady calculation. When ACH is low, the heat transfer rate increases continuously with time. When ACH becomes higher, the heat transfer rate increases and decreases with time. When ACH is quite high, there exists a large difference in the heat transfer rate between the steady and unsteady calculations, which emphasizes the importance of the unsteady calculation.