Mobile QR Code QR CODE : Korean Journal of Air-Conditioning and Refrigeration Engineering
Korean Journal of Air-Conditioning and Refrigeration Engineering

Korean Journal of Air-Conditioning and Refrigeration Engineering

ISO Journal TitleKorean J. Air-Cond. Refrig. Eng.
  • Open Access, Monthly
Open Access Monthly
  • ISSN : 1229-6422 (Print)
  • ISSN : 2465-7611 (Online)
Title Analysis of Saving Rates according to Energy Consumption Factors in Office Building
Authors Byung-Il Park ; In-Ho Yang
DOI http://dx.doi.org/10.6110/KJACR.2016.28.3.115
Page pp.115-122
ISSN 1229-6422
Keywords 사무소 건물 ; 에너지 절감 요소 ; 절감률 ; 분석 Office building ; Energy reduction factor ; Saving rate ; Analysis
Abstract In this study, 21 energy reduction factors were selected as architecture, system & operation, and lighting and equipment parts to analyze reduction method of the load occurring in office buildings. Energy consumption simulation was performed. In the architecture part, saving rate (1.53%) of “occupant density” factor was the most efficient. In the system and operation part, saving rate (1.28%) of “interior VAV and exterior FPU type” factor was the most efficient. In case of lighting and equipment part, saving rate (12.42%) of “schedule” factor was the most efficient. In the three parts, saving rate of the lighting and equipment part was 27.32%. This was caused by the “schedule” factor. Saving rates of the architecture part and the system and operation part were 3.39% and 1.20%, respectively.