Title |
A Study on Thermal Analysis for a Data Center Cooling System under Fault Conditions at a Chilled Water Plant |
DOI |
http://dx.doi.org/10.6110/KJACR.2016.28.5.178 |
Keywords |
데이터센터 ; 냉방시스템 ; 냉열원 ; 열성능평가 ; 열원중단 비상시 ; 전산유체역학 Data center ; Cooling system ; Chilled water plant ; Thermal analysis ; Under fault condition ; CFD simulation |
Abstract |
This study describes the analysis of a 20 MW chilled water plant used for the IT cooling of a recently constructed data center in Korea. The CFD model was developed with the aim of evaluating the impact of problems such as chiller failure on the water and air temperatures in the cooling system. The numerical model includes the chilled water hydraulic network and individual water-to-air CRAC units. The coupling between the IT server room air temperature levels and the cooling plant has enabled a full assessment of the cooling system design in response to system fault conditions to be performed. The paper examines an emergency situation involving the failure of the cooling plant, and shows how the inherent thermal inertia of the system along with additional inertia achieved through buffer systems allowed a suitable design to be achieved. |