Mobile QR Code QR CODE : Korean Journal of Air-Conditioning and Refrigeration Engineering
Korean Journal of Air-Conditioning and Refrigeration Engineering

Korean Journal of Air-Conditioning and Refrigeration Engineering

ISO Journal TitleKorean J. Air-Cond. Refrig. Eng.
  • Open Access, Monthly
Open Access Monthly
  • ISSN : 1229-6422 (Print)
  • ISSN : 2465-7611 (Online)
Title Evaluation of Floor Heating Performance and Design Criteria for Operating an Outdoor Swimming Pool During Winter : A Case Study
Authors Jinkyun Cho ; Kyunghun Woo ; Jin-Ho Kim
DOI https://dx.doi.org/10.6110/KJACR.2017.29.6.289
Page pp.289-296
ISSN 1229-6422
Keywords 옥외수영장 ; 바닥난방시스템 ; 결빙방지 ; 3차원 전열해석 ; 열용량 Outdoor swimming pool ; Floor heating system ; Anti-freezing ; 3-dimensional heat transfer analysis ; Thermal capacity
Abstract This study aimed to analyze the deck floor heating system of an outdoor swimming pool in terms of the thermal capacity/output and the surface temperature distribution based on the outdoor temperature, to design for anti-freezing during winter. Through the transient heat transfer simulation with PHYSIBEL and theoretical equations, the surface temperature distribution of the floor heating system at two outdoor conditions in Jeju, were calculated and evaluated. The results indicate that the specific thermal output required for maintaining 4℃ surface temperature at the design outdoor temperature of 0.1℃, was about 90 W/m2. This performance analysis can be applied for future design criteria, including optimizations of system capacity and size.