Title The Performance Improvement of a Gas Injection Heat Pump with a Flash Tank
Authors Kilsoo Son ; Dongwoo Kim ; Sungkyung Choi ; Yongchan Kim
DOI https://dx.doi.org/10.6110/KJACR.2017.29.6.297
Page pp.297-305
ISSN 1229-6422
Keywords 가스인젝션 ; 기액분리기 ; 로터리 압축기 ; 히트펌프 Gas injection ; Flash Tank ; Rotary Compressor ; Heat Pump
Abstract Air-source heat pumps are widely used in residential heating systems. However, the decrease in the capacity of the heat pump is unavoidable when operating at very low and high ambient temperatures. The vapor injection technique is considered a promising technology to overcome this problem. Recent research on vapor injection cycles have mainly adopted a scroll compressor with an internal heat exchanger at severe operating conditions. This study measured the COP and EER of a gas injection heat pump using a flash tank with an inverter-driven rotary compressor at severe operating conditions. Compared to non-injection heat pumps, the heating capacity and COP of the gas injection heat pump improved up to 15% and 2.9%, respectively, at outdoor temperatures of -10℃ to 7℃. The cooling capacity of the gas injection heat pump was 11% higher than the non-injection heat pump at an outdoor temperature of 35℃. At the same time, the EER of the gas injection heat pump was similar to that of the non-injection heat pump.