Title |
A Study on the Limitation and Improvement of Simple Window Model applied to EnergyPlus |
DOI |
https://doi.org/10.6110/KJACR.2017.29.10.515 |
Keywords |
단순창호모델 ; 에너지플러스 ; 열해석 ; 내부유입율 Simple window model ; EnergyPlus ; Thermal analysis ; Inward flowing fraction |
Abstract |
EnergyPlus, which is widely used in various fields, provides Simple Window Model, a window model that can be used practically. However, the results of building load using the model are different from those of the standard model. The main cause of the deviation by Simple Window Model was analyzed to be due to the assumption that all windows were considered as single layer. The purpose of this study is to propose a window model that improves the cause of deviation by Simple Window Model and can be easily calculated from the algebraic relations. The proposed window model solved the heat balance equation algebraically by using seven window characteristic coefficients. The coefficient relationships consisted of the heat transmission coefficient and solar heat gain coefficient as input parameters make practical use and calculation possible. As a result of comparing the deviation between each window model by implementing the dynamic analysis method, the proposed window model showed that the deviation of the total heating/cooling energy consumption was reduced to 1/3 compared to Simple Window Model for one year. Although the maximum energy consumption did not show any significant improvement, the indoor temperature evaluation showed significantly reduced deviation. |