Mobile QR Code QR CODE : Korean Journal of Air-Conditioning and Refrigeration Engineering
Korean Journal of Air-Conditioning and Refrigeration Engineering

Korean Journal of Air-Conditioning and Refrigeration Engineering

ISO Journal TitleKorean J. Air-Cond. Refrig. Eng.
  • Open Access, Monthly
Open Access Monthly
  • ISSN : 1229-6422 (Print)
  • ISSN : 2465-7611 (Online)
Title Experimental Study on the Effects of Seawater Fouling on a Plate-Frame Heat Exchanger
Authors Won Keun Baik ; Jaehyeok Heo ; Rin Yun
DOI https://doi.org/10.6110/KJACR.2018.30.5.205
Page pp.205-210
ISSN 1229-6422
Keywords 해수 ; 파울링 ; 판형 열교환기 ; 총괄열전달계수 ; 열전달계수 ; 압력강하 Seawater ; Fouling ; Plate heat exchanger ; Overall heat transfer coefficient ; Heat transfer coefficient ; Pressure drop
Abstract Two plate type heat exchangers were tested. One was under fouling conditions from seawater and the other was under clean condition. Overall heat coefficient, heat transfer coefficient, fouling thermal resistance, and pressure drop of the heat exchangers were obtained. Effects of fouling on plate type heat exchangers were then investigated. The test heat exchanger, a differential pressure transducer, and two mass flow meters were installed. The working fluid used in the experiment was water on the seawater side and brine on the other side of the heat exchanger. Operational temperatures for seawater side were 10℃, 20℃, and 30℃. The brine side temperatures were 5℃, 15℃, and 25℃. Operational flow rates at both sides were 20-30 lpm. The overall heat transfer coefficient for seawater side was increased by an average of 21% in clean condition without fouling. Pressure drop was less than 2 kPa with temperature variation. However, pressure drop for seawater side was increased four times under fouling conditions.