Mobile QR Code QR CODE : Korean Journal of Air-Conditioning and Refrigeration Engineering
Korean Journal of Air-Conditioning and Refrigeration Engineering

Korean Journal of Air-Conditioning and Refrigeration Engineering

ISO Journal TitleKorean J. Air-Cond. Refrig. Eng.
  • Open Access, Monthly
Open Access Monthly
  • ISSN : 1229-6422 (Print)
  • ISSN : 2465-7611 (Online)
Title Mock-up Test Applicate to Phase Change Material in Floor Radiant Heating System
Authors Tae Won Kim ; Young Kwon Yang ; Hwan-Sik Kim ; Jin Chul Park
DOI https://doi.org/10.6110/KJACR.2018.30.11.497
Page pp.497-507
ISSN 1229-6422
Keywords 바닥 복사 난방 ; 상변화물질 ; 실물모형 Floor radiant heating ; Phase change material ; Mock-up
Abstract This study represent an experimental study of PCM floor radiant heating system. The results obtained from the study are summarized as follows; 1) PCM floor radiant heating system is an inser-tion of a 10 mm thick PCM into the existing standard floor structure, which has the advantage of good construct ability due to no additional process. 2) It was confirmed that the PCM thread remains higher than the normal room. In particular, it was found that the temperature of hot water pipes under the pipes was maintained at 36℃ or higher after four hours after the boiler was stopped. Therefore, we have seen that the room temperature of the PCM floor radiant heating system is longer than the general floor heating system, PCM Floor Radiant Heating is considered to improve the comfort of indoor residents.