Mobile QR Code QR CODE : Korean Journal of Air-Conditioning and Refrigeration Engineering
Korean Journal of Air-Conditioning and Refrigeration Engineering

Korean Journal of Air-Conditioning and Refrigeration Engineering

ISO Journal TitleKorean J. Air-Cond. Refrig. Eng.
  • Open Access, Monthly
Open Access Monthly
  • ISSN : 1229-6422 (Print)
  • ISSN : 2465-7611 (Online)
Title Water Vapor Adsorption and Heat Transfer Characteristics of FAPO Zeolite Adsorbent Coating Plate with Operating Conditions
Authors Kyung Jin Bae ; Oh Kyung Kwon
DOI https://doi.org/10.6110/KJACR.2021.33.8.377
Page pp.377-384
ISSN 1229-6422
Keywords 흡착제; 흡착특성; 수분흡착량; 코팅; 열전달량; 총괄열전달계수 Adsorbent; Adsorbent characteristics; Amount of adsorbent; Coating; Heat transfer rate; Overall heat transfer coefficient
Abstract Adsorption chillers have attracted considerable attention as they are energy saving and environmentally friendly systems. In this paper, water vapor adsorption experiments of adsorbent coating plate were performed in a batch type adsorption apparatus. The adsorbent and refrigerant used for the experiment were FAPO (FerroAluminoPhOsphate) and water, respectively. Four operating conditions of the adsorbent coating plate, including binder ratio, coating thickness, evaporator temperature, and adsorption bed temperature were used in the experiment. Experimental results showed that the adsorbent coating plate gave the best binder ratio of 10%, coating thickness of 0.2 mm, and adsorption time of 7 min. it was also found that evaporator temperature of 14℃ and adsorption bed temperature of 25℃ showed better performance in adsorption rate than other evaporator temperatures (6℃, 10℃) and adsorption bed temperatures (30℃, 35℃).