Mobile QR Code QR CODE : Korean Journal of Air-Conditioning and Refrigeration Engineering
Korean Journal of Air-Conditioning and Refrigeration Engineering

Korean Journal of Air-Conditioning and Refrigeration Engineering

ISO Journal TitleKorean J. Air-Cond. Refrig. Eng.
  • Open Access, Monthly
Open Access Monthly
  • ISSN : 1229-6422 (Print)
  • ISSN : 2465-7611 (Online)
Title A Study on the Ventilation Performance Affected by the Location of the Supply Louver and the Induction Fan Installed in the Underground Parking Lot
Authors Yong-Il Kwon
DOI https://doi.org/10.6110/KJACR.2022.34.5.218
Page pp.218-227
ISSN 1229-6422
Keywords 유인팬; 급기루버; 급기구 기여율; 환기효율 Induction fan; Supply louver; SVE4; Ventilation performance
Abstract Since many people live in large cities in Korea, buildings built in the downtown areas of such cities are being constructed as high-rise buildings. Additionally, to use the land efficiently, the parking lot for many vehicles is built underground, and is enlarged and multi-storied. It is critical that such a facility has an adequate ventilation function, to dilute as well as filter the exhaust gas of the vehicles as well as a smoke control function, to remove fire pollutants. The purpose of this study was to evaluate the effect of the location of the supply louver or the induction fan installed for ventilation of an underground parking lot, applied to apartment houses and commercial buildings pursuant to ventilation performance. In conclusion, the contribution of the induction fan to the improvement of ventilation performance increases as the air change rate decreases, and it is critical to consider the uniform arrangement of the supply air louvers as the air change rate increases.