Title Experimental and Numerical Study on Energy Performance and Thermal Stability of an Immersion Cooling in Data Center
Authors Jikyum Kim ; Jinkyun Cho ; Joo Hyun Moon ; Hoseung Han ; Seongho Kim ; Ha Neol Kim
DOI https://doi.org/10.6110/KJACR.2026.38.10.537
Page pp.537-546
ISSN 1229-6422
Keywords 전산유동해석; 데이터 센터; 현장실험; 단상액침냉각 CFD; Data Center; In-situ Measurement; Single-phase Immersion Cooling
Abstract This study evaluates the energy performance and thermal stability of an immersion-cooled data center system under realistic operating conditions. A system-scale experimental facility two 40 kW immersion cooling providing a total IT load of approximately 80 analysis and PUE were The system a plate heat exchanger the primary chilled-water loop from the secondary dielectric oil loop andoperated under a single-chiller condition. Power consumption and inlet/outlet temperatures were measured at 10-second intervals over two hours, during which the PUE remained within range of 1.1.28. CFD simulations were performed for a single server installed in the immersion cooling tank, nine of 440 W each, all heat source temperatures below 85°C. These results indicate that immersion cooling can achieve both high energy efficiency and reliable thermal management in high-density data center environments.