Title |
Effect of the Vertical Air Circulation on the Thermal Environment in a Large Space |
Authors |
김경환 ; 강석윤 ; 최충현 ; 조영진 ; 이재헌 ; 오명도 |
Keywords |
Vertical air circulation ; 수직순환기류 ; Thermal comfort ; 열적 쾌적 ; Jet fan ; 제트팬 ; Predicted Percentage of Dissatisfied ; PPD:예상불만족률 ; Large space ; 대공간 |
Abstract |
This paper describes the effect of vertical air circulation on the thermal environment in an airport passenger terminal with induced flow by jet fans. In comparing the level of thermal comfort at the breathing line of 1.5 m in height, the results from the two models with or without the vertical air circulation, show that the average PPD is 8% in the former and 23% in the latter, respectively. It is thought that vertical air circulation lends to improved thermal comfort for human in respect of ventilation in a large space. |