Title |
An Experimental Study on the Oil Circulation in an Inverter-Driven Heat Pump |
Authors |
민만기 ; 홍기수 ; 황윤제 ; 황일남 ; 김철민 ; 조관식 |
Keywords |
Inverter-driven heat pump ; 인버터 열펌프 ; Refrigerant/oil mixture ; 냉매/오일 혼 합물 ; Oil concentration ; 오일농도 ; Density monitoring system ; 밀도계 |
Abstract |
It is important to investigate characteristics of flow of refrigerant/oil mixture circulating in a refrigeration system. Therefore the oil concentration in refrigerant/oil mixture should be measured exactly by the adequate measuring instrument. In this paper, the oil concentration was measured by density monitoring system(DMS) in the liquid-line of a inverter-driven heat pump. Experimental result follows ; the main factor that have an effect on oil concentration refrigerant/oil mixture circulating in a refrigeration system is the momentum and kinematic viscosity of refrigerant/oil mixture compressed by scroll compressor. |