Title A Study of Surge Pressure Absorption by Water Hammer Arrester in Water Supply Piping System
Authors 이용화 ; 유지오
Page pp.1066-1072
ISSN 12296422
Keywords Water hammer arrester ; 워터 햄머 흡수기 ; Solenoid valve ; 솔레노이드 밸브 ; Valve closure ; 밸브폐쇄 ; Pressure history ; 압력변동 ; Maximum and minimum pressure ; 최대 및 최저압력
Abstract This study is to investigate the pressure wave characteristics and the absorption of maximum and minimum pressure generated by instantaneous valve closure at the end of the straightening copper piping system with and without a water hammer arrester. Experiments were conducted under the following conditions : initial pressure 1∼5 bar, flow velocity 0.6∼3.0 m/s, water temperature 20℃ and air volume of water hammer arrester 80∼180 cm3. Experimental results show that the optimum air volume of water hammer arrester is 110 cm3.