Mobile QR Code QR CODE : Korean Journal of Air-Conditioning and Refrigeration Engineering
Korean Journal of Air-Conditioning and Refrigeration Engineering

Korean Journal of Air-Conditioning and Refrigeration Engineering

ISO Journal TitleKorean J. Air-Cond. Refrig. Eng.
  • Open Access, Monthly
Open Access Monthly
  • ISSN : 1229-6422 (Print)
  • ISSN : 2465-7611 (Online)
Title Analysis on the Thermal Characteristics of Variable Conductance Heat Pipe
Authors 김근오 ; 김무근 ; 박병규
Page pp.38-47
ISSN 12296422
Keywords Heat pipe ; 히트파이프 ; Variable conductance ; 가변 컨덕턴스 ; Non-condensible gas ; 불응축가스 ; Control sensitivity ; 제어 감도
Abstract The operation characteristics of variable conductance heat pipe (VCHP) were numerically investigated by using 1-dimensional diffuse-front model. For different boundary conditions, the amount of non-condensible gas charge and dimension of gas reservoir were obtained by iterative calculation. It is found that the amount of non-condensible gas charge and dimensions of gas reservoir have an effect on the temperature control of condenser for the given operating condition of VCHP. The numerical results show that the VCHP has an excellent capability of temperature control when subjected to a change in the heat input.