Title Cooling Performance Measurement of a 3 Room Type Inverter Heat Pump System
Authors 정광진 ; 최영돈 ; 장효환 ; 송재복 ; 박윤철
Page pp.431-441
ISSN 12296422
Keywords 전자팽창밸브 ; 전자팽창밸브 ; 열 ; 다실형 열펌프 시스템 ; 단속운전 ; Multi-room heat pump system ; Electronic expansion valve ; Cyclic operation
Abstract Recently, multi-room type heat pump system has aroused much attention, because it can achieve much reduction of installation cost and space as well as energy saving in companion with the single room type heat pump system.
In the present study, performance characteristics of a 3 room type inverter driven heat pump system, which is widely spread in Japanese market, are measured. In the single room operation, performances of a heat pump system such as the difference of compressor outlet and inlet pressures and the mass flowrate may increase with the increase of cooling capacity so that COP of the system decrease with the increase of cooling capacity. However, in the 2 room operation, mass flowrate and COP of the total system increase makedly as compared with the single room operation.