Title |
Analysis of Temperature and Humidity Distribution in a Dry Room |
Keywords |
Dry room ; 저습 공조실 ; Moisture contamination ; 수분 오염 ; 3D numerical analysis ; 3차원 수치해석 |
Abstract |
The temperature and humidity distributions in a dry room are studied numerically by using standard turbulence model. In order to evaluate effective heat and moisture ventilation characteristics inside the room, the heat removal capacity and moisture exhaust efficiency are introduced. An effective ventilation control is analyzed by evaluating quantitatively temperature and humidity distributions. It was found that the mean absolute humidity inside the room was almost constant with approximately 0.1905 g/kg air regardless of the models and the heat generation rates. This was believed that the moisture generation by workers was relatively small. 40% improvement of the critical decay time was achieved, through the modifications of design variables. |