Mobile QR Code QR CODE : Korean Journal of Air-Conditioning and Refrigeration Engineering
Korean Journal of Air-Conditioning and Refrigeration Engineering

Korean Journal of Air-Conditioning and Refrigeration Engineering

ISO Journal TitleKorean J. Air-Cond. Refrig. Eng.
  • Open Access, Monthly
Open Access Monthly
  • ISSN : 1229-6422 (Print)
  • ISSN : 2465-7611 (Online)
Title Application of the Outdoor Air Temperature Prediction Control for Intermittent Heating Residences
Authors 태춘섭 ; 조성환 ; 이충구
Page pp.682-691
ISSN 12296422
Keywords Intermittent heating ; 간헐난방 ; 난방 ; Outdoor air temperature prediction control ; 외기온도 예측제어 ; 온도
Abstract Most of radiant floor heating systems are operated in the intermittent heating mode in Korea. The application possibility of predictive suboptimal control for Korean residential house was investigated by computer simulation and experiment. For this study, TRNSYS program was used and an experimental facility consisting of two rooms (3×4.4×2.8 m) identical in construction was built. The facility enabled simultaneous comparison of two different control method. And real multi residential house was investigated.Results showed that outdoor air temperature prediction control was superior to the conventional control for radiant floor heating system operated in the intermittent heating mode. New control system resulted in good thermal environment and less energy consumption.