• 대한전기학회
Mobile QR Code QR CODE : The Transactions of the Korean Institute of Electrical Engineers
  • COPE
  • kcse
  • 한국과학기술단체총연합회
  • 한국학술지인용색인
  • Scopus
  • crossref
  • orcid
Title Absorption Current Ratio and Impedance Hybrid Method of Fault Location for AC Railway Power Supply System
Authors 김효두(Hyo Doo Kim) ; 창상훈(Sang Hoon Chang)
DOI https://doi.org/10.5370/KIEE.2025.74.12.2387
Page pp.2387-2392
ISSN 1975-8359
Keywords Fault Locator; Absorption current ratio method; Reactance method; Auto-transformers
Abstract Due to the construction of new sections, existing overhead catenary systems are interconnected, there is no auto-transformers at the very end. In these last zone without AT at the very end, it is not possible to identify the fault location using conventional methods even if a ground fault occurs. When a ground fault occurs in such the last zone, the fault current is mostly absorbed by a AT located in the front side of the last zone. This characteristic is used to determine the fault zone. Since it is not possible to calculate the current ratio based on distance in the last zone, a reactance-based method is employed to pinpoint the fault location. In other zones, the existing absorption current ratio method is used.