The main challenge in the existing protection system is the long coordination time
                  interval between the downstream and upstream relay and the lack of communications
                  between the protective devices that results in cascading failure. the existing protection
                  and control system was reviewed and upgraded to Make sure the interlocking between
                  the chiller and lubrication pump motor. In addition the following countermeasures
                  also can be considered to improve design vulnerability of the existing protection
                  system; 
                  
               
               
                  ⓵ Quick detection of the temperature rise before insulation failure using IEC 61850
                  with smart sensors.
                  
               
               
                  ⓶ Logical Interlocking by implementation of IEC61850 substation automation protocol.
                  
               
               
                  ⓷ Apply breaker failure protection scheme using digital relays based IEC61850.
                  
               
               
                  Recently constructed NPPs applied digital relays and existing NPPs also getting retrofit
                  the analog relay with digital relays so, peer to peer communication between relays
                  can be applied without additional equipment installations and make it possible to
                  apply above mentioned solutions.
                  
               
               
                     3.1 Existing Electrical Protection and Control System
                  	
                     The current protection coordination for the central chiller motor pump is achieved
                     using time over current relay (51) for incoming feeders, and instantaneous time overcurrent
                     relay (50) and time overcurrent relay (51) for branch feeders. The coordination time
                     interval (CTI) between the downstream and the upstream protection devices has to be
                     considered and followed According to IEEE, the CTI between downstream and upstream
                     protection devices, should be about 200~250 ms. This CTI cause late trip of the upstream
                     circuit breaker when the circuit breaker of downstream relay fails to trip[4][5]. The existing fault clearing time by the circuit breaker of the upstream feeder relay
                     in case of failure of the CB of the downstream relay can be calculated as shown in
                     Table 1;
                     
                  
                  
                     
                     
                     
                           
                           
Table 1. Fault clearing time by circuit breaker.
                        
                        
                           
                           
                                 
                                    
                                       | Action | Clearing time | 
                                 
                                       | Downstream relay trip time | 40 ms | 
                                 
                                       | Lockout relay operation | 8 ms | 
                                 
                                       | Five cycle CB | 83 ms | 
                                 
                                       | CTI between downstream and upstream relay | 250 ms | 
                                 
                                       | Total time | 381 ms | 
                              
                           
                        
                      
                     
                  
                  
                     As shown in Fig. 5 when a fault occurs in the motor feeder circuit it would take 131 ms for the CB of
                     the downstream relay (50) up to 381 ms of the CB of the upstream relay to pick up
                     and clear the fault, that means in case of downstream CB failure to trip, the fault
                     occurred in the motor continued about 381 ms until the upstream CB pickup and remove
                     the fault, resulted in release of substantial thermal energy during short circuit
                     fault causing thermal overheating of the motor stator windings.
                     
                  
                  
                     
                     
                           
                           
Fig. 5. Fault clearing time curve
                         
                     
                  
                  
                     The existing relay coordination curve between downstream and upstream circuit breakers
                     for the central chiller water pump motor circuit of Hanbit NPP unit (2) was shown
                     in Fig. 6.
                     
                  
                  
                     In the following paragraphs, there is going to be much more explanation about improvement
                     of the existing electrical protection system to prevent cascading failure in NPP’s
                     electrical protection power system.
                     
                  
                
               
                     3.3 Prevention of Cascading Failure Using IEC61850
                  	
                     IEC 61850 is a communication protocol that can give many benefits to the NPP electric
                     power system, not only cost savings but also design improvement. However, in the MV
                     system of NPPs, electrical system protection is relying on the time-current curve
                     (TCC) coordination in the case of overcurrent fault. Using IEC61850 can significantly
                     reduce communication time, which is critical when the fault occurs. IEC 61850 provides
                     fast communication by using designated communication types; MMS, GOOSE and SV [6]. GOOSE is the fastest message among the three types of IEC 61850 communication types
                     by using 2 OSI layers only. GOOSE message is especially for the urgent actions like
                     trip, interlocking signals. On the other hand, Korean NPPs have applied digital relays
                     since Shin-Kori 3&4 nuclear power plant. The digital relay is intelligent electronic
                     device and it supports IEC 61850 communication functions. So, communication between
                     IEDs with IEC 61850 is applicable on the MV system without additional device installation
                     [7].
                     
                  
                  3.3.1 Communication-Based Breaker Failure Protection
                  
                     The IEC61850 based GOOSE scheme allows continuous communication between IEDs, once
                     the overcurrent relay detects a fault, it initiates a direct transfer trip (DTT) signal
                     to the upstream circuit breaker to clear the fault [8]. DTT needs to be dependable during fault conditions to allow the trip signal to be
                     received correctly. This type of peer to peer communications based breaker failure
                     protection can be applied in different ways:
                     
                  
                  
                     • As a function in IEDs that initiates the breaker failure protection when it receives
                     the trip signal from the relay protecting the faulted power system equipment. 
                     
                  
                  
                     • As a built-in function in the protective IED that detected the fault and issued
                     the trip signal.
                     
                  
                  3.3.2 Implementation of Circuit Breaker Failure in IEC 61850 environment
                  
                     Fig. 7 shows the data communication between relays using IEC61850 environment, when a fault
                     occurs in the downstream feeder. The downstream relay will detect a fault and will
                     issue a tripping GOOSE message to clear the fault. The CBF function will respond to
                     these GOOSE message and the breaker failure timer will start. In case of breaker failure,
                     the breaker failure function will point out this failure and a GOOSE message will
                     be sent over the LAN network to trip upstream breakers and initiate DTT to the upstream
                     relay to clear the fault. When the IED initiates a trip signal, it starts a timer
                     and monitoring the CB current. If the current does not go away in a predefined time,
                     the IED issues a re-trip or trips the upstream breakers to isolate the faulted one.
                     After the downstream relay gets a tripping signal but doesn’t received tripping signal
                     from the breaker, the downstream relay shall send a breaker failure initiate signal
                     (BFI) through a GOOSE message to the upstream relay to force it to trip the upstream
                     circuit breaker, nevertheless the blocking timer has expired or not [9]. 
                     
                  
                  
                     
                     
                           
                           
Fig. 7. Data communication between relays
                         
                     
                  
                  
                     In order to achieve this kind of communication, IEC61850 defines specific protective
                     features as (LN), a specific category of specified attributes to each logical node
                     are also defined. LN can also be currently located in different types of IEDs. Calculations
                     of voltage, current and condition are transmitted to the relays via a process bus
                     that is an ethernet channel of communication. The RBRF class is confined to circuit
                     breaker failure (CBF) protection as per IEC61850-7-4, see Table 2. The IEC61850 standard documents define the attributes, (OpIn) corresponds to re-trip
                     order from the RBRF to the broken CB (stage I or inner trip), (OpEx) corresponds to
                     the corresponding breaker tripping command (stage II or external trip), And FailMod
                     deals with the assessment of breaker malfunction by current status,  This LN's specifications
                     are described in IEC 61850 part 5.
                     
                  
                  
                     
                     
                     
                           
                           
Table 2. Class assigned to CBF
                        
                        
                           
                           
                                 
                                    
                                       | Attribute | Discription | class | 
                                 
                                       | Class | RBRF | 
                                 
                                       | OpCntRs | Operation re-set counter | 
                                 
                                       | Details about the condition | 
                                 
                                       | Str | ACD | Start, timer running | 
                                 
                                       | OpEx | ACT | BF trip (“External trip”) | 
                                 
                                       | OpIn | ACT | BF trip (“Internal trip”) | 
                                 
                                       | Settings | 
                                 
                                       | StrVal | ASG | Start Value | 
                                 
                                       | FailMod | ING | BF Mode detection. | 
                                 
                                       | FailTmms | ING | BF Time Delay for downstream trip. | 
                                 
                                       | ReTrMod | ING | Retrip Mode. | 
                              
                           
                        
                      
                     
                  
                  
                     In case of fault, LN transfer a message to the RBRF (initiated by the CBF), and the
                     RBRF triggers the timer. The RBRF gives a message via the network to the XCBRs (logical
                     node for circuit breaker) to trip the upstream CB if the downstream breaker fails
                     to trip / clear the fault. All upstream XCBR register to and receive this message
                     at the same time to implement next required actions. The RBRF information communication
                     with other logical nodes is shown in Figure 8. Blocks IHMI, CALH, ITCI, RBRF, XCBR
                     and Pxyz are logical nodes ((Pxyz stands for the main protection (e.g., PIOC for instantaneous
                     overcurrent)); Table 3 gives functional descriptions of each logical nodes.
                     
                  
                  
                     
                     
                     
                           
                           
Table 3. Functional descriptions of logical nodes
                        
                        
                           
                           
                                 
                                    
                                       | Logical Nodes | Functional Descriptions | 
                                 
                                       | IHMI | Human Machine Interface | 
                                 
                                       | CALH | Fault indication and Alarm signal | 
                                 
                                       | ITCI | Tele-controlling application | 
                                 
                                       | RBRF | Breaker failure | 
                                 
                                       | XCBR | Circuit Breaker | 
                                 
                                       | PIOC | Instantaneous overcurrent protection | 
                                 
                                       | PTOC | Time overcurrent protection | 
                              
                           
                        
                      
                     
                  
                  
                     The RBRF receives from the protection LNs a trigger signal. The RBRF transmits four
                     kinds of signals:
                     
                  
                  
                     • Data about the fault is transmitted via IHMI and ITCI.
                     
                  
                  
                     • trip indication transmitted through IHMI, ITCI and CALH.
                     
                  
                  
                     • Settings are sent to IHMI and ITCI.
                     
                  
                  
                     • All subscribed breakers (XCBR) receive Trip Commands through PIOC, PTOC and a coordination
                     signal was published through CILO signal.
                     
                  
                  
                     The first three classes of signals were transmitted to upstream logical nodes, which
                     are indicators to monitor and record bay-level events. The last signals are defensive
                     and the most important.as reliable communication links between the RBRF and the XCBRs
                     subscribed are highly essential [10].
                     
                  
                  
                     
                     
                           
                           
Fig. 8. Data Communication between RBRF and other logical nodes
                         
                     
                  
                  3.3.3 IEC61850 based zone selective interlocking
                  
                     ZSI is based on currents comparison between protective zones. It has a communication
                     control logic system between downstream and upstream breakers. The IEC61850 GOOSE
                     based ZSI scheme always concern about blocking time. It is used to improve the level
                     of protection in the electrical protection power system, through communication between
                     protective relays across the protected zones to reduce the fault clearing time. During
                     ground fault or phase fault conditions the protective devices electronic interlocking
                     allows the devices close to the fault to override its preset time delay automatically
                     and clear the fault without intentional time delay [11]. As illustrated in Fig. 9, when a short circuit fault occurs at the central chiller motor, both the faulted
                     downstream relay and the upstream relay detect the fault. In order to block tripping
                     the main breaker (NB-S02-01) and avoid loss of power for the whole bus, the faulted
                     downstream relay of the CB (NB-S02-18) sends a blocking signal to block the upstream
                     relay from tripping the upstream main CB (NB-S02-01) and averting the whole bus power
                     losses. After fault clearance, fault is not detected any more, but if a fault is not
                     cleared and both the downstream feeder relay and upstream relay still detecting the
                     fault, the main upstream relay will trip the main CB (NB-S02-01) as a backup protection.
                     
                     
                  
                  
                     
                     
                           
                           
Fig. 9. Protection coordination scheme using ZSI
                         
                     
                  
                  
                     The result is that other devices remain unaffected by the fault and the fault is cleared
                     more rapidly than the existing protection system without using ZSI. The main advantage
                     of applying IEC61850 based ZSI is to reduce blocking time between the downstream and
                     upstream relay to its minimum without affecting relays operations. Accordingly, we
                     need to consider the opening time and communication time between the downstream CB
                     (NB-S02-18) and the upstream CB (NB-S02-01) that requires extended blocking time to
                     give the feeder breakers a time to operate first and isolate the fault. For majority
                     of the relays the internal rationale execution time from overcurrent relays to pick
                     up the fault till the time to send a GOOSE messaging within 2 ms up to 10ms based
                     on network traffics, it is also the same from receiving a GOOSE to trip the upstream
                     breaker. The relay contact responding time is about 8 ms. If we consider medium voltage
                     five-cycle circuit breaker that would add additional (83ms) for 60Hz system. Depending
                     on network configuration and design, the overall travelling time among the downstream
                     relay and the main upstream relay depending on the distance between the relays and
                     the Ethernet network would be about 20 ms  [12]. So, the fault clearing time between the downstream and upstream feeder relays using
                     ZSI can be calculated as shown in Table 4;
                     
                  
                  
                     
                     
                     
                           
                           
Table 4. Fault clearing time using IEC61850 based ZSI
                        
                        
                           
                           
                                 
                                    
                                       | Action | Clearing time | 
                                 
                                       | Downstream relay trip time | 40 ms | 
                                 
                                       | Lockout relay operation | 8 ms | 
                                 
                                       | Five cycle CB | 83 ms | 
                                 
                                       | Communication signal travelling time between downstream and upstream relay | 20 ms | 
                                 
                                       | Total time | 151 ms | 
                              
                           
                        
                      
                     
                  
                  
                     As a result, by applying IEC61850 based ZSI, the fault clearing time of the upstream
                     CB would be 151 ms for five cycle CB. This time is quite greatly faster compared to
                     the existing protection time 381 ms which results in decreasing the motor thermal
                     overheating caused by short circuit fault current.