Mobile QR Code QR CODE : Korean Journal of Air-Conditioning and Refrigeration Engineering
Korean Journal of Air-Conditioning and Refrigeration Engineering

Korean Journal of Air-Conditioning and Refrigeration Engineering

ISO Journal TitleKorean J. Air-Cond. Refrig. Eng.
  • Open Access, Monthly
Open Access Monthly
  • ISSN : 1229-6422 (Print)
  • ISSN : 2465-7611 (Online)
Title Performance Characteristics of Type Ⅱ LiBr-H2O Absorption Heat Pump in Accordance with the Refrigerant Heat Exchanger Configuration
Authors Chang Hyun Lee ; Jun Seong Yoon ; In Gwan Kim ; Oh Kyung Kwon ; Dong An Cha ; Kyung Jin Bae ; Min Su Kim ; Chan Woo Park
DOI https://dx.doi.org/10.6110/KJACR.2017.29.7.373
Page pp.373-384
ISSN 1229-6422
Keywords 흡수식 히트펌프 ; 냉매 열교환기 ; 성적계수 ; 물/리튬브로마이드 ; 히트 트렌스포머 Absorption heat pump ; Refrigerant heat exchanger ; COP ; H2O/LiBr ; Heat transformer
Abstract The objective of this study was to determine the effect of refrigerant heat exchanger on the performance of type II absorption heat pump performance using numerical analysis. Two heat exchange installation methods were used: solution to refrigerant and waste hot water to refrigerant. These methods were compared to the standard model of hot water flow without using refrigerant heat exchanger. When waste hot waters were bypassed to refrigerant heat exchanger, COP was not affected. However, steam mass generation rates were increased compared to those of the standard model. When solutions were bypassed to the refrigerant heat exchanger, results were different depending on the place where the solution rejoined. COP and steam mass generation rates were lower compared to those when waste heat water was passed to refrigerant heat exchanger. Thus, it is possible to obtain higher steam mass generation rates by using waste water and installing refrigerant heat exchanger.