이송우
                     (Song-Woo Lee)
                     1
                     김영일
                     (Young-Il Kim)
                     2†
                     김선혜
                     (Sean-Hay Kim)
                     3
               
                  - 
                           서울과학기술대학교 에너지환경대학원 박사과정
                        (Ph.D. Candidate, Graduate School of Energy and Environment, Seoul National University
                        of Science & Technology, Seoul, 01811, Korea)
                        
 
                  - 
                           서울과학기술대학교 건축학부 교수
                        (Professor, School of Architecture, Seoul National University of Science & Technology, Seoul, 01811, Korea)
                        
 
                  - 
                           서울과학기술대학교 건축학부 교수
                        (Professor, School of Architecture, Seoul National University of Science & Technology, Seoul, 01811, Korea)
                        
 
               
             
            
            
            Copyright © 2016, Society of Air-Conditioning and Refrigeration Engineers of Korea
            
            
            
            
            
               
                  
Key words
               
               공동주택(Apartment), 중앙식 냉난방시스템(Centralized cooling and heating system), 신재생에너지(New renewable energy), 지열원 히트펌프(Geothermal heat pump), 초기투자비(Initial investment cost)
             
            
          
         
            
                  1. 서론
                
               우리나라의 공동주택은 1970년대 이후 고도 경제성장에 따른 개발도상국의 특징인 팽창 일변도의 양적 성장단계를 거쳐, 1990년대 후반부터 본격적인
               시장경제 개념이 적용되고 있다. 이러한 변화는 경제수준의 향상과 함께 주거환경 개선에 대한 수요자의 요구에 기인한 것으로, 공동주택이 기존의 단순한
               주거개념에서 벗어나 삶의 질을 결정짓는 중요한 요소 중의 하나로 자리 잡게 되었음을 의미한다. 최근 국내뿐만 아니라 국외에서도 관심이 높아지고 있는
               건축물의 에너지절약 및 친환경성에 대한 요소와 결합되어, 온실가스의 배출이 적고 화석연료의 사용량이 적은, 에너지비용에 대한 절감요소가 적용된 공동주택에
               대한 설계가 요구되고 있으며, 국내 건축물에 적용되는 신재생에너지 의무적용 기준(서울시 환경영향평가 심의기준)을 살펴보면, 신재생에너지 사용량이 총
               에너지사용량의 4%로 향후 2023년에는 10%까지 확대되는 등 공동주택 단지 내 신재생에너지의 이용 패러다임이 변화하고 있다.  
               
               
 
               이런 패러다임을 고려하여 최근 공동주택의 냉난방시스템은 개별식 냉난방시스템에서 중앙식 냉난방시스템으로의 변경이 고려되고 있다. 중앙식 냉난방시스템
               관련 연구로 Lee et al.
(1)은 중앙식 난방시스템의 난방열 사용량을 측정하고 데이터를 비교 및 분석하였으며 이를 통하여 향후 에너지절약 설계기준을 예상하였다. 또한 Lee et
               al.
(2)는 중앙식 난방시스템을 적용한 공동주택의 에너지원별 원단위 사례분석을 통해 정부의 에너지정책 수립 및 에너지절약적 설계를 위한 기초자료를 제공하였다.
               기존의 중앙 냉난방시스템은 단지 내 세대를 제외한 공용시설 냉난방을 위해 냉온수를 공급하는 방식이 주로 적용되었으나 최근 고려되고 있는 사항으로는
               단지 내 공용시설 뿐만 아니라 모든 세대의 냉난방을 위해 냉온수 공급시스템 적용이 논의되고 있다. 이렇게 중앙 냉난방시스템을 적용하고 열에너지를 신재생에너지로
               공급하는 방안에 대한 협의가 이루어지고 있으며, 에너지절약적이고 친환경적인 시스템을 구현하는 것을 목표로 하고 있다. 이에 본 연구에서는 공동주택을
               대상으로 중앙 냉난방시스템을 적용하기 위한 기계설비 분야의 적용방안, 고려사항 등을 검토하여 적용 가능한 시스템을 선정하고, 선정된 시스템의 초기투자비를
               통한 경제성 분석을 수행하여 보았다. 
               
               
 
             
            
                  2. 연구개요
                
               국내 대부분의 일반건축물은 사용패턴이 단순하고 획일화되어 있어 중앙 냉난방시스템을 주로 적용하고 있으며, 열원의 종류가 사용패턴에 영향을 미치지 않기
               때문에 정부의 규제 및 인센티브, 각종 인증의 이점을 위해 적극적으로 신재생에너지를 이용한 열원시스템을 적용하고 있다. 
               
               
 
               반면 공동주택의 경우에는 재실자의 사용패턴 다양성, 시공 및 유지관리의 용이성 등을 이유로 세대 내 개별보일러와 EHP 등을 설치하는 개별 냉난방시스템이
               보편화되어 있으며, 일부 지역난방 고시지역의 경우 의무적으로 중온수를 열원으로 이용하는 지역 냉난방시스템을 적용하고 있어 공동주택의 신재생에너지 적용에
               한계가 있다. 하지만 최근 에너지절약, 시설 안전성 향상, 주거건물에서의 신재생에너지기기 설치 의무 비율 상승 등으로 중앙 냉난방시스템이 고려되고
               있으며, 특히 서울시의 경우에는 2023년까지 신재생에너지 설치비율을 10%까지 적용하는 것을 목표로 하고 있어 공동주택을 대상으로 신재생에너지를
               적용할 수 있는 중앙 냉난방시스템에 대한 검토가 필요하다. 위의 
Table 1은 서울시의 주거건물 신재생에너지 설치 의무 비율 변화를 기술한 것이다. 본 연구에서는 
Table 2와 같이 공동주택 개별 냉난방시스템과 중앙 냉난방시스템의 특징을 간단하게 비교하고, 공동주택에 적용 가능한 중앙 냉난방시스템 검토모델을 선정하여 보았다.
               공동주택 중앙 냉난방시스템 검토 시에는 지역 냉난방시스템을 제외하였으며, 이것은 지역난방 열사용시설 기준에 신재생 에너지와 중복사용이 제한되기 때문이다.
               
               
 
               
                     Table 1. The Criteria of new and renewable energy installation percentage for residential buildings in Seoul
                   
                     
                           
                              
                                 | 
                                    
                                 			
                                  Year 
                                 			
                               | 
                              
                                    
                                 			
                                  '13 
                                 			
                               | 
                              
                                    
                                 			
                                  '15 
                                 			
                               | 
                              
                                    
                                 			
                                  '16 
                                 			
                               | 
                              
                                    
                                 			
                                  '17 
                                 			
                               | 
                              
                                    
                                 			
                                  '18 
                                 			
                               | 
                              
                                    
                                 			
                                  '19 
                                 			
                               | 
                              
                                    
                                 			
                                  '20 
                                 			
                               | 
                              
                                    
                                 			
                                  '21 
                                 			
                               | 
                              
                                    
                                 			
                                  '22 
                                 			
                               | 
                              
                                    
                                 			
                                  '23 
                                 			
                               | 
                           
                        
                        
                              
                                 | 
                                    
                                 			
                                  Ratio 
                                 			
                               | 
                              
                                    
                                 			
                                  1% 
                                 			
                               | 
                              
                                    
                                 			
                                  2% 
                                 			
                               | 
                              
                                    
                                 			
                                  3% 
                                 			
                               | 
                              
                                    
                                 			
                                  4% 
                                 			
                               | 
                              
                                    
                                 			
                                  5% 
                                 			
                               | 
                              
                                    
                                 			
                                  6% 
                                 			
                               | 
                              
                                    
                                 			
                                  7% 
                                 			
                               | 
                              
                                    
                                 			
                                  8% 
                                 			
                               | 
                              
                                    
                                 			
                                  9% 
                                 			
                               | 
                              
                                    
                                 			
                                  10% 
                                 			
                               | 
                           
                        
                     
 
                  
                
                
               
                     Table 2. Comparison of cooling and heating system in apartment
                   
                     
                           
                              
                                 | 
                                    
                                 			
                                  Classification 
                                 			
                               | 
                              
                                    
                                 			
                                  Individual cooling and heating system 
                                 			
                               | 
                              
                                    
                                 			
                                  Centralized cooling and heating system 
                                 			
                               | 
                           
                        
                        
                              
                                 | 
                                    
                                 			
                                  Concept 
                                 			
                               | 
                              
                                    
                                 			
                                  ∙Circulation of refrigerant through multiple indoor and outdoor units. 
                                 
                                 			
                                 ∙Heat and domestic hot water supplied by individual heating system 
                                 			
                               | 
                              
                                    
                                 			
                                  ∙A large capacity boiler installed in the central mechanical room supplies heat and
                                    domestic hot water through pipes.
                                  
                                 			
                               | 
                           
                           
                                 | 
                                    
                                 			
                                  Space 
                                 			
                               | 
                              
                                    
                                 			
                                  ∙Separate boiler and outdoor unit room should be installed. 
                                 
                                 			
                                 ∙No centralized mechanical space required 
                                 			
                               | 
                              
                                    
                                 			
                                  ∙A separate chilled water and hot water supply piping installation space is required. 
                                 
                                 			
                                 ∙No individual boiler space required 
                                 			
                               | 
                           
                           
                                 | 
                                    
                                 			
                                  Maintenance 
                                 			
                               | 
                              
                                    
                                 			
                                  ∙Tenant must manage the facility directly. Professional engineer is needed in case
                                    of failure.
                                  
                                 
                                 			
                                 ∙Additional expense incurs in case of failure 
                                 
                                 			
                                 ∙Durability and replacement cycle are short. 
                                 			
                               | 
                              
                                    
                                 			
                                  ∙Facility worker required for continuous maintenance. 
                                 
                                 			
                                 ∙High maintenance cost 
                                 
                                 			
                                 ∙Requires accurate flow control for varying loads 
                                 			
                               | 
                           
                           
                                 | 
                                    
                                 			
                                  Efficiency 
                                 			
                               | 
                              
                                    
                                 			
                                  ∙Low energy loss 
                                 			
                               | 
                              
                                    
                                 			
                                  ∙High pipe heat loss and preheat load 
                                 			
                               | 
                           
                           
                                 | 
                                    
                                 			
                                  Construction 
                                 			
                               | 
                              
                                    
                                 			
                                  ∙Piping and construction processes are simple, resulting in short construction period. 
                                 			
                               | 
                              
                                    
                                 			
                                  ∙Difficult construction and long construction period due to complicated piping 
                                 			
                               | 
                           
                           
                                 | 
                                    
                                 			
                                  Cost 
                                 			
                               | 
                              
                                    
                                 			
                                  ∙Low construction cost due to less cooling/heating piping. 
                                 			
                               | 
                              
                                    
                                 			
                                  ∙High construction cost due to centralized mechanical room and cooling/heating piping 
                                 			
                               | 
                           
                        
                     
 
                  
                
                
             
            
                  3. 연구내용
               
                     3.1 중앙 냉난방시스템 검토모델 선정 
                   
                  공동주택에 적용 가능한 중앙 냉난방시스템 검토모델 선정에 앞서 공동주택의 냉난방 부하패턴을 알아보기 위해 실제 사용 중인 A공동주택을 대상으로 실측데이터로
                  시간대별 부하율을 분석해보았다. 
Table 3은 A공동 주택의 2015년 실측데이터로 냉방기간(6월 1일~8월 18일), 난방기간(1월 1일~3월 31일)을 요약한 것이다. 
Table 3과 같이 공동주택의 시간대별 부하율을 살펴보면 주거를 목적으로 하는 건물이기 때문에 24시간 부하가 발생하는 것으로 나타났으며, 주간시간 부하율이
                  낮게, 야간 및 심야시간에 부하율이 높게 나타남을 알 수 있다. 또한 냉방기간에는 시간지연(time lag)에 의한 축열부하에 따라 오후 3시경 부하율이
                  높아지고 있으며, 반대로 난방기간에는 오후 3시경 부하율이 낮아지는데 이는 태양의 일사로 인한 열이 단위세대로 유입되며 냉방 및 난방에 영향을 미쳤기
                  때문으로 판단된다.
                  
                  
 
                  
                        Table 3. Cooling and heating loads
                      
                        
                              
                                 
                                    | 
                                       
                                    			
                                     Time 
                                    			
                                  | 
                                 
                                       
                                    			
                                     Cooling load 
                                    			
                                  | 
                                 
                                       
                                    			
                                     Heating load 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Maximum load 
                                    			
                                  | 
                                 
                                       
                                    			
                                     Load ratio 
                                    			
                                  | 
                                 
                                       
                                    			
                                     Maximum load 
                                    			
                                  | 
                                 
                                       
                                    			
                                     Load ratio 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     kW 
                                    			
                                  | 
                                 
                                       
                                    			
                                     % 
                                    			
                                  | 
                                 
                                       
                                    			
                                     kW 
                                    			
                                  | 
                                 
                                       
                                    			
                                     % 
                                    			
                                  | 
                              
                           
                           
                                 
                                    | 
                                       
                                    			
                                     1H 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.241 
                                    			
                                  | 
                                 
                                       
                                    			
                                     78.40 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.314 
                                    			
                                  | 
                                 
                                       
                                    			
                                     84.40 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     2H 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.209 
                                    			
                                  | 
                                 
                                       
                                    			
                                     68.14 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.291 
                                    			
                                  | 
                                 
                                       
                                    			
                                     78.14 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     3H 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.222 
                                    			
                                  | 
                                 
                                       
                                    			
                                     72.16 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.291 
                                    			
                                  | 
                                 
                                       
                                    			
                                     78.14 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     4H 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.235 
                                    			
                                  | 
                                 
                                       
                                    			
                                     76.23 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.279 
                                    			
                                  | 
                                 
                                       
                                    			
                                     75.01 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     5H 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.270 
                                    			
                                  | 
                                 
                                       
                                    			
                                     87.82 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.279 
                                    			
                                  | 
                                 
                                       
                                    			
                                     75.01 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     6H 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.184 
                                    			
                                  | 
                                 
                                       
                                    			
                                     59.89 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.279 
                                    			
                                  | 
                                 
                                       
                                    			
                                     75.01 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     7H 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.202 
                                    			
                                  | 
                                 
                                       
                                    			
                                     65.63 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.326 
                                    			
                                  | 
                                 
                                       
                                    			
                                     87.52 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     8H 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.145 
                                    			
                                  | 
                                 
                                       
                                    			
                                     47.17 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.337 
                                    			
                                  | 
                                 
                                       
                                    			
                                     90.65 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     9H 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.237 
                                    			
                                  | 
                                 
                                       
                                    			
                                     77.21 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.302 
                                    			
                                  | 
                                 
                                       
                                    			
                                     81.27 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     10H 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.137 
                                    			
                                  | 
                                 
                                       
                                    			
                                     44.53 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.279 
                                    			
                                  | 
                                 
                                       
                                    			
                                     75.01 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     11H 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.213 
                                    			
                                  | 
                                 
                                       
                                    			
                                     69.32 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.279 
                                    			
                                  | 
                                 
                                       
                                    			
                                     75.01 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     12H 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.191 
                                    			
                                  | 
                                 
                                       
                                    			
                                     61.85 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.233 
                                    			
                                  | 
                                 
                                       
                                    			
                                     62.53 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     13H 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.169 
                                    			
                                  | 
                                 
                                       
                                    			
                                     54.69 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.198 
                                    			
                                  | 
                                 
                                       
                                    			
                                     53.15 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     14H 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.220 
                                    			
                                  | 
                                 
                                       
                                    			
                                     71.27 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.209 
                                    			
                                  | 
                                 
                                       
                                    			
                                     56.28 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     15H 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.259 
                                    			
                                  | 
                                 
                                       
                                    			
                                     84.09 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.174 
                                    			
                                  | 
                                 
                                       
                                    			
                                     46.89 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     16H 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.244 
                                    			
                                  | 
                                 
                                       
                                    			
                                     79.23 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.209 
                                    			
                                  | 
                                 
                                       
                                    			
                                     56.24 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     17H 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.234 
                                    			
                                  | 
                                 
                                       
                                    			
                                     75.90 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.209 
                                    			
                                  | 
                                 
                                       
                                    			
                                     56.24 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     18H 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.241 
                                    			
                                  | 
                                 
                                       
                                    			
                                     78.05 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.267 
                                    			
                                  | 
                                 
                                       
                                    			
                                     71.88 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     19H 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.274 
                                    			
                                  | 
                                 
                                       
                                    			
                                     89.33 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.314 
                                    			
                                  | 
                                 
                                       
                                    			
                                     84.40 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     20H 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.274 
                                    			
                                  | 
                                 
                                       
                                    			
                                     89.23 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.349 
                                    			
                                  | 
                                 
                                       
                                    			
                                     93.74 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     21H 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.230 
                                    			
                                  | 
                                 
                                       
                                    			
                                     74.68 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.360 
                                    			
                                  | 
                                 
                                       
                                    			
                                     96.91 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     22H 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.253 
                                    			
                                  | 
                                 
                                       
                                    			
                                     82.42 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.372 
                                    			
                                  | 
                                 
                                       
                                    			
                                     100.00 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     23H 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.284 
                                    			
                                  | 
                                 
                                       
                                    			
                                     92.38 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.349 
                                    			
                                  | 
                                 
                                       
                                    			
                                     93.78 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     24H 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.277 
                                    			
                                  | 
                                 
                                       
                                    			
                                     89.96 
                                    			
                                  | 
                                 
                                       
                                    			
                                     0.326 
                                    			
                                  | 
                                 
                                       
                                    			
                                     87.52 
                                    			
                                  | 
                              
                           
                        
 
                     
                   
                   
                  이러한 공동주택 사용패턴을 고려하여 
Table 4와 같이 검토모델을 선정하였으며, 열을 축열하지 않고 바로 이용하는 일반적인 열 모델, 심야전기를 이용하여 부하 측에 공급 후 남는 잉여열을 축열하여
                  주간에 공급하는 축열모델, 열병합발전기를 이용한 열+전기 복합 모델의 3가지로 구분하였다. 3가지 모델은 공통적으로 신재생에너지인 지열히트펌프를 적용하였다.
                  
                  
 
                  
                        Table 4. Three study cases of centralized cooling and heating system
                      
                        
                              
                                 
                                    | 
                                       
                                    			
                                     Cases 
                                    			
                                  | 
                                 
                                       
                                    			
                                     Components 
                                    			
                                  | 
                              
                           
                           
                                 
                                    | 
                                       
                                    			
                                     Heat 
                                    			
                                  | 
                                 
                                       
                                    			
                                     TH-NS 
                                    			
                                  | 
                                 
                                       
                                    			
                                     GSHP+boiler+chiller 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Heat storage 
                                    			
                                  | 
                                 
                                       
                                    			
                                     TH-US 
                                    			
                                  | 
                                 
                                       
                                    			
                                     GSHP+boiler+chiller+heat storage tank 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Complex 
                                    			
                                  | 
                                 
                                       
                                    			
                                     CP-NS 
                                    			
                                  | 
                                 
                                       
                                    			
                                     GSHP+small-scale cogeneration plants+chiller 
                                    			
                                  | 
                              
                           
                        
 
                     
                   
                   
                  또한 냉난방 부하면적 대상은 전용면적 84 m
2 65세대를 기준으로 적용하였으며 기준 부하량 분석은 겨울철 3개월, 여름철 2.5개월간 실측에 의한 운전 데이터를 근거로 하였다.
                  
                  
 
                
               
                     3.1 장비용량 산출을 위한 부하계산 기준 설정
                   
                  검토모델의 초기투자비 비교분석을 위해서는 냉난방시스템 설계와 함께 적용된 설비기기들의 용량 및 대수가 필요하다. 하지만 해당 작업은 공동주택 규모와
                  환경, 기타 시스템 등에 크게 영향을 받아 변동성이 크므로 비교는 주 냉난방기기로 한정하였다. 
                  
                  
 
                  주 냉난방기기 용량 산출을 위해서 본 연구에서는 서울 종로구에 실제 계획된 공동주택을 참고하여 가상의 B공동주택을 계획하고 부하계산을 산출하였다.
                  
Table 5는 B공동주택의 개요를 나타낸 것이다.
                  
                  
 
                  
                        Table 5. Overview of B apartment
                      
                        
                              
                                 
                                    | 
                                       
                                    			
                                     Classification 
                                    			
                                  | 
                                 
                                       
                                    			
                                     Value 
                                    			
                                  | 
                              
                           
                           
                                 
                                    | 
                                       
                                    			
                                     Zone 1 
                                    			
                                  | 
                                 
                                       
                                    			
                                     Area 
                                    			
                                  | 
                                 
                                       
                                    			
                                     38,876 m2 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Number of household 
                                    			
                                  | 
                                 
                                       
                                    			
                                     514 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Number of stories 
                                    			
                                  | 
                                 
                                       
                                    			
                                     19F 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Zone 2 
                                    			
                                  | 
                                 
                                       
                                    			
                                     Area 
                                    			
                                  | 
                                 
                                       
                                    			
                                     35,280 m2 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Number of household 
                                    			
                                  | 
                                 
                                       
                                    			
                                     420 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Number of stories 
                                    			
                                  | 
                                 
                                       
                                    			
                                     20F 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Zone 3 
                                    			
                                  | 
                                 
                                       
                                    			
                                     Area 
                                    			
                                  | 
                                 
                                       
                                    			
                                     23,108 m2 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Number of household 
                                    			
                                  | 
                                 
                                       
                                    			
                                     212 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Number of stories 
                                    			
                                  | 
                                 
                                       
                                    			
                                     18F 
                                    			
                                  | 
                              
                           
                        
 
                     
                   
                   
                  중앙 냉난방시스템의 설계 구체화를 위해 기초 데이터 분석을 통한 단위 냉난방부하, RTS-SAREK 프로그램을 이용해 산출된 단위 냉난방부하, 지역난방공사
                  등의 열사용시설기준, 설비공학편람 및 건축설비 관련 전문도서 등을 참고하여 본 연구에서 적용할 수 있도록 표준 단위면적당 냉난방부하를 산정하였으며,
                  조닝별 냉난방부하 산출 결과는 
Table 6과 같다.
                  
                  
 
                  
                        Table 6. Cooling and heating loads
                      
                        
                              
                                 
                                    | 
                                       
                                    			
                                     Classification 
                                    			
                                  | 
                                 
                                       
                                    			
                                     Number of household 
                                    			
                                  | 
                                 
                                       
                                    			
                                     Cooling load 
                                    			
                                  | 
                                 
                                       
                                    			
                                     Heating load 
                                    			
                                  | 
                              
                           
                           
                                 
                                    | 
                                       
                                    			
                                     kW 
                                    			
                                  | 
                                 
                                       
                                    			
                                     kW 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Zone 1 
                                    			
                                  | 
                                 
                                       
                                    			
                                     514 
                                    			
                                  | 
                                 
                                       
                                    			
                                     2,413 
                                    			
                                  | 
                                 
                                       
                                    			
                                     2,627 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Zone 2 
                                    			
                                  | 
                                 
                                       
                                    			
                                     420 
                                    			
                                  | 
                                 
                                       
                                    			
                                     2,162 
                                    			
                                  | 
                                 
                                       
                                    			
                                     2,354 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Zone 3 
                                    			
                                  | 
                                 
                                       
                                    			
                                     212 
                                    			
                                  | 
                                 
                                       
                                    			
                                     1,317 
                                    			
                                  | 
                                 
                                       
                                    			
                                     1,434 
                                    			
                                  | 
                              
                           
                        
 
                     
                   
                   
                
               
                     3.3 검토 모델별 장비 선정
                  
                        3.3.1 지열원 히트펌프 용량 선정
                      
                     앞서 산출된 B공동주택의 조닝별 냉난방부하 산출 결과를 토대로 3개의 검토모델에 공통적으로 적용되는 지열원 히트펌프의 용량을 선정해 보았다.
                     
                     
 
                     일반적인 업무용 건물에서의 부하계산시에는 냉방 최대부하가 난방 최대부하보다 높게 나타나 냉방 부하 기준으로 열원설비를 선정한다. 이는 부하계산 조건
                     중 내부 발열요소(인체, 조명, 기기부하)가 난방시에는 도움 요소로 적용되지만, 냉방부하에서는 부하 증가의 요인이 된다. 하지만 공동주택에서는 난방부하가
                     냉방부하 보다 높게 산정되며, 이는 공동주택의 특성상 주간의 부하율이 높지 않기 때문이다. 공동주택은 운영특성상 야간시간의 부하율이 더 높으며, 난방시
                     더 낮은 외기온도로 인해 난방부하가 상승하는 요인이 된다. 이러한 특성을 고려하여 본 연구에서는 열원기기 선정을 위해 냉방부하가 아닌 난방부하를 기준으로
                     하였다. 히트펌프 용량은 서울시에서 계획하고 있는 신재생에너지 설치 비율 10% 이상을 만족하기 위해 최대부하의 70% 용량으로 지열원 히트펌프를
                     선정하였으며, 
Table 7은 지열원 히트펌프 선정내용을 나타낸 것이다.
                     
                     
 
                     
                           Table 7. Calculated and selected capacity of geothermal heat pump
                         
                           
                                 
                                    
                                       | 
                                          
                                       			
                                        Zone 
                                       			
                                     | 
                                    
                                          
                                       			
                                        Calculated 
                                       			
                                     | 
                                    
                                          
                                       			
                                        Selected 
                                       			
                                     | 
                                 
                                 
                                       | 
                                          
                                       			
                                        Heating load 
                                       			
                                     | 
                                    
                                          
                                       			
                                        Ratio 
                                       			
                                     | 
                                    
                                          
                                       			
                                        Capacity 
                                       			
                                     | 
                                    
                                          
                                       			
                                        Cooling capacity 
                                       			
                                     | 
                                    
                                          
                                       			
                                        Heating capacity 
                                       			
                                     | 
                                    
                                          
                                       			
                                        Number 
                                       			
                                     | 
                                 
                                 
                                       | 
                                          
                                       			
                                        kW 
                                       			
                                     | 
                                    
                                          
                                       			
                                        % 
                                       			
                                     | 
                                    
                                          
                                       			
                                        kW 
                                       			
                                     | 
                                    
                                          
                                       			
                                        USRT 
                                       			
                                     | 
                                    
                                          
                                       			
                                        kW 
                                       			
                                     | 
                                    
                                          
                                       			
                                        EA 
                                       			
                                     | 
                                 
                              
                              
                                    
                                       | 
                                          
                                       			
                                        1 
                                       			
                                     | 
                                    
                                          
                                       			
                                        2,627.9 
                                       			
                                     | 
                                    
                                          
                                       			
                                        70 
                                       			
                                     | 
                                    
                                          
                                       			
                                        1,839.5 
                                       			
                                     | 
                                    
                                          
                                       			
                                        522.5 
                                       			
                                     | 
                                    
                                          
                                       			
                                        1,845.6 
                                       			
                                     | 
                                    
                                          
                                       			
                                        11 
                                       			
                                     | 
                                 
                                 
                                       | 
                                          
                                       			
                                        2 
                                       			
                                     | 
                                    
                                          
                                       			
                                        2,354.7 
                                       			
                                     | 
                                    
                                          
                                       			
                                        70 
                                       			
                                     | 
                                    
                                          
                                       			
                                        1,648.3 
                                       			
                                     | 
                                    
                                          
                                       			
                                        475.0 
                                       			
                                     | 
                                    
                                          
                                       			
                                        1,677.9 
                                       			
                                     | 
                                    
                                          
                                       			
                                        10 
                                       			
                                     | 
                                 
                                 
                                       | 
                                          
                                       			
                                        3 
                                       			
                                     | 
                                    
                                          
                                       			
                                        1,435.0 
                                       			
                                     | 
                                    
                                          
                                       			
                                        70 
                                       			
                                     | 
                                    
                                          
                                       			
                                        1,006.7 
                                       			
                                     | 
                                    
                                          
                                       			
                                        285.0 
                                       			
                                     | 
                                    
                                          
                                       			
                                        1,006.7 
                                       			
                                     | 
                                    
                                          
                                       			
                                        6 
                                       			
                                     | 
                                 
                              
                           
 
                        
                      
                      
                   
                  
                        3.3.2 TH-NS 모델 
                      
Fig. 1은 TH-NS 모델의 개요를 나타낸 것으로 지열원 히트펌프는 난방시 바닥난방의 표면온도를 고려하여 45℃의 온수를 생성하여 부하측으로 공급하고, 냉방시
                     7℃의 냉수를 부하측으로 공급한다. 적용된 온수보일러는 부하측의 사용을 위해 열교환기를 적용하여 지열원 히트펌프와 동일한 45℃의 온수로 열교환한다.
                     냉방시에는 냉동기에서 생성되는 냉수 온도가 지열원 히트펌프와 동일한 7℃로 설정되어 별도의 열교환기 없이 부하측으로 공급되도록 하였다.
                     
                     
 
                     
                           Fig. 1. Overview of TH-NS model.
 
                      
                     TH-NS 모델의 지열원 히트펌프는 지중열을 이용하는 시스템으로 냉방시 지중으로 열을 방출하고, 난방시 지중의 열을 흡수한다. 이로 인해 지중으로의
                     영향을 검토하여 시스템의 가동시간을 결정하여야 하며, 일반적으로 하루 12시간 내외의 가동시간으로 설정한다. 업무용 건물의 경우 건물의 운영시간이
                     12시간 내외로 계획되어 지열원 히트펌프를 적용하더라도 지중으로의 영향을 크게 고려하지 않아도 되지만, 공동주택의 경우 24시간 내내 부하가 발생하는
                     특성으로 인해, 지열원 히트펌프를 업무용 건물과 같이 적용할 경우 지중열의 불균형을 초래할 수 있다. 냉방기간 과도한 방열로 인해 지중의 온도는 지속적으로
                     상승하고, 온도가 상승된 지중열로 인해 시스템의 효율이 저하될 수 있는 문제점을 가지고 있다.
                     
                     
 
                     이러한 특성을 고려하여 24시간 동안 지열원 히트펌프를 가동하지 않는 방향으로 지열원 히트펌프의 운영계획을 수립하였으며, 선정된 지열원 히트펌프를
                     2개의 부분으로 계획하여 1개의 부분은 주간부하를 담당하고, 나머지 1개 부분은 야간부하를 담당하도록 하였다. 
                     
                     
 
                     TH-NS 모델은 온수보일러와 스크류냉동기를 통해 전체부하 중 지열원 히트펌프에서 공급하는 열량을 제외한 나머지 열량을 공급하도록 계획하였다. 전체부하의
                     70%에 해당하는 지열원 히트펌프 용량을 주간과 야간으로 약 35%씩 분할하였으므로 부하처리를 위한 나머지 65%의 용량을 보일러와 냉동기가 대응할
                     수 있도록 
Table 8과 같이 선정하였으며, 순차기동이 가능하고 고장시를 고려하여 50% 용량 2대로 대수분할을 계획하였다. 
                     
                     
 
                     
                           Table 8. Boiler and chiller specification of TH-NS
                         
                           
                                 
                                    
                                       | 
                                          
                                       			
                                        Zone 
                                       			
                                     | 
                                    
                                          
                                       			
                                        Boiler 
                                       			
                                     | 
                                    
                                          
                                       			
                                        Chiller 
                                       			
                                     | 
                                 
                                 
                                       | 
                                          
                                       			
                                        Heating load 
                                       			
                                     | 
                                    
                                          
                                       			
                                        GSHP capacity 
                                       			
                                     | 
                                    
                                          
                                       			
                                        Capacity 
                                       			
                                     | 
                                    
                                          
                                       			
                                        Cooling load 
                                       			
                                     | 
                                    
                                          
                                       			
                                        GSHP capacity 
                                       			
                                     | 
                                    
                                          
                                       			
                                        Capacity 
                                       			
                                     | 
                                 
                                 
                                       | 
                                          
                                       			
                                        kW 
                                       			
                                     | 
                                    
                                          
                                       			
                                        kW 
                                       			
                                     | 
                                    
                                          
                                       			
                                        kW 
                                       			
                                     | 
                                    
                                          
                                       			
                                        USRT 
                                       			
                                     | 
                                    
                                          
                                       			
                                        USRT 
                                       			
                                     | 
                                    
                                          
                                       			
                                        USRT 
                                       			
                                     | 
                                 
                              
                              
                                    
                                       | 
                                          
                                       			
                                        1 
                                       			
                                     | 
                                    
                                          
                                       			
                                        2,627.9 
                                       			
                                     | 
                                    
                                          
                                       			
                                        880.5 
                                       			
                                     | 
                                    
                                          
                                       			
                                        1,747.4 
                                       			
                                     | 
                                    
                                          
                                       			
                                        686.4 
                                       			
                                     | 
                                    
                                          
                                       			
                                        259.5 
                                       			
                                     | 
                                    
                                          
                                       			
                                        426.9 
                                       			
                                     | 
                                 
                                 
                                       | 
                                          
                                       			
                                        2 
                                       			
                                     | 
                                    
                                          
                                       			
                                        2,354.7 
                                       			
                                     | 
                                    
                                          
                                       			
                                        880.5 
                                       			
                                     | 
                                    
                                          
                                       			
                                        1,474.2 
                                       			
                                     | 
                                    
                                          
                                       			
                                        615.0 
                                       			
                                     | 
                                    
                                          
                                       			
                                        259.5 
                                       			
                                     | 
                                    
                                          
                                       			
                                        355.5 
                                       			
                                     | 
                                 
                                 
                                       | 
                                          
                                       			
                                        3 
                                       			
                                     | 
                                    
                                          
                                       			
                                        1,435.0 
                                       			
                                     | 
                                    
                                          
                                       			
                                        528.3 
                                       			
                                     | 
                                    
                                          
                                       			
                                        906.7 
                                       			
                                     | 
                                    
                                          
                                       			
                                        374.8 
                                       			
                                     | 
                                    
                                          
                                       			
                                        155.7 
                                       			
                                     | 
                                    
                                          
                                       			
                                        219.1 
                                       			
                                     | 
                                 
                              
                           
 
                        
                      
                      
                   
                  
                        3.3.3 TH-US 모델
                      
Fig. 2는 TH-US 모델의 개요를 나타낸 것이다. TH-NS 모델과 달리 축열조가 추가된 형태이며, 축열조를 제외한 장비의 선정은 동일한 조건으로 설정하였다.
                     TH-US 모델은 축열조가 추가되어 TH-NS와 다르게 운영된다. TH-US 모델은 TH-NS 모델과 마찬가지로 일반 지열히트펌프, 온수보일러를 적용하였으며,
                     보일러의 온수 출구온도를 45℃로 설정할 수 없어 열교환기를 통해 45℃의 온수를 공급하도록 설정하였다.
                     
                     
 
                     
                           Fig. 2. Overview of TH-US model.
 
                      
                     비축열 방식인 TH-NS 모델은 지열원 히트펌프를 주간과 야간으로 구분하여 별도로 운영하였지만, 축열 방식인 TH-US 모델은 지열원 히트펌프는 주간과
                     야간으로 구분하지 않고, 야간에만 가동되도록 설정하였다. 지열원 히트펌프는 전기 외에 별도의 에너지를 소비하지 않으며, 심야전기로 구분되는 22~08시
                     동안 가동 한다. 이때, 난방과 냉방에 따라 보일러와 냉동기도 함께 가동되고 심야시간에는 모든 장비가 100% 부하로 운전되어 열을 축열한다. 
                     
 
                     심야시간에 장비가 가동하여 생성되는 열은 먼저 부하측으로 공급되고, 부하측으로 공급되지 못하고 남는 잉여열은 축열조로 저장하도록 하였다. 주간시간에는
                     야간에 축열된 열을 부하측으로 공급하고, 부족한 열은 보일러, 냉동기를 가동해 공급하는 것으로 계획하였다.
                     
                     
 
                     TH-US 모델의 보일러 및 냉동기는 앞서 분석된 TH-NS 모델과 동일하게 선정하였으며, 누계 축열량 검토를 통해 최적의 장비용량이 되도록 분석하였다.
                     
Table 9는 열원설비 용량 산정을 위해 산출한 부하를 나타낸 것이다. 보일러는 에너지절약 및 유지관리의 용이성을 위해 50% 용량의 2대로 대수분할을 계획하였다.
                     
                     
 
                     
                           Table 9. Boiler and chiller specification of TH-US
                         
                           
                                 
                                    
                                       | 
                                          
                                       			
                                        Zone 
                                       			
                                     | 
                                    
                                          
                                       			
                                        Boiler 
                                       			
                                     | 
                                    
                                          
                                       			
                                        Chiller 
                                       			
                                     | 
                                 
                                 
                                       | 
                                          
                                       			
                                        Heating load 
                                       			
                                     | 
                                    
                                          
                                       			
                                        Ratio 
                                       			
                                     | 
                                    
                                          
                                       			
                                        Capacity 
                                       			
                                     | 
                                    
                                          
                                       			
                                        Cooling load 
                                       			
                                     | 
                                    
                                          
                                       			
                                        Ratio 
                                       			
                                     | 
                                    
                                          
                                       			
                                        Capacity 
                                       			
                                     | 
                                 
                                 
                                       | 
                                          
                                       			
                                        kW 
                                       			
                                     | 
                                    
                                          
                                       			
                                        % 
                                       			
                                     | 
                                    
                                          
                                       			
                                        kW 
                                       			
                                     | 
                                    
                                          
                                       			
                                        USRT 
                                       			
                                     | 
                                    
                                          
                                       			
                                        % 
                                       			
                                     | 
                                    
                                          
                                       			
                                        USRT 
                                       			
                                     | 
                                 
                              
                              
                                    
                                       | 
                                          
                                       			
                                        1 
                                       			
                                     | 
                                    
                                          
                                       			
                                        2,627.9 
                                       			
                                     | 
                                    
                                          
                                       			
                                        60 
                                       			
                                     | 
                                    
                                          
                                       			
                                        1576.76 
                                       			
                                     | 
                                    
                                          
                                       			
                                        522.5 
                                       			
                                     | 
                                    
                                          
                                       			
                                        50 
                                       			
                                     | 
                                    
                                          
                                       			
                                        343.18 
                                       			
                                     | 
                                 
                                 
                                       | 
                                          
                                       			
                                        2 
                                       			
                                     | 
                                    
                                          
                                       			
                                        2,354.7 
                                       			
                                     | 
                                    
                                          
                                       			
                                        60 
                                       			
                                     | 
                                    
                                          
                                       			
                                        1412.84 
                                       			
                                     | 
                                    
                                          
                                       			
                                        475.0 
                                       			
                                     | 
                                    
                                          
                                       			
                                        50 
                                       			
                                     | 
                                    
                                          
                                       			
                                        307.50 
                                       			
                                     | 
                                 
                                 
                                       | 
                                          
                                       			
                                        3 
                                       			
                                     | 
                                    
                                          
                                       			
                                        1,435.0 
                                       			
                                     | 
                                    
                                          
                                       			
                                        60 
                                       			
                                     | 
                                    
                                          
                                       			
                                        861.00 
                                       			
                                     | 
                                    
                                          
                                       			
                                        285.0 
                                       			
                                     | 
                                    
                                          
                                       			
                                        50 
                                       			
                                     | 
                                    
                                          
                                       			
                                        187.39 
                                       			
                                     | 
                                 
                              
                           
 
                        
                      
                      
Table 10은 누계 축열량 검토를 통해 분석된 난방 및 냉방 축열량, 축열조 최소용량을 나타낸 것이다. Zone 1~3의 누계 축열량 분석 결과 냉방의 누계
                     축열량이 높게 나타났으며, 냉방을 기준으로 축열조의 최소용량을 산정하였다.
                     
                     
 
                     
                           Table 10. Heat storage tank capacity
                         
                           
                                 
                                    
                                       | 
                                          
                                       			
                                        Zone 
                                       			
                                     | 
                                    
                                          
                                       			
                                        Heating 
                                       			
                                     | 
                                    
                                          
                                       			
                                        Cooling 
                                       			
                                     | 
                                    
                                          
                                       			
                                        Objective 
                                       			
                                     | 
                                    
                                          
                                       			
                                        Minimum capacity 
                                       			
                                     | 
                                 
                                 
                                       | 
                                          
                                       			
                                        kWh/day 
                                       			
                                     | 
                                    
                                          
                                       			
                                        kWh/day 
                                       			
                                     | 
                                    
                                          
                                       			
                                        kWh/day 
                                       			
                                     | 
                                 
                              
                              
                                    
                                       | 
                                          
                                       			
                                        1 
                                       			
                                     | 
                                    
                                          
                                       			
                                        12,109.73 
                                       			
                                     | 
                                    
                                          
                                       			
                                        13,866.42 
                                       			
                                     | 
                                    
                                          
                                       			
                                        Cooling 
                                       			
                                     | 
                                    
                                          
                                       			
                                        13,866.42 
                                       			
                                     | 
                                 
                                 
                                       | 
                                          
                                       			
                                        2 
                                       			
                                     | 
                                    
                                          
                                       			
                                        11,091.42 
                                       			
                                     | 
                                    
                                          
                                       			
                                        12,028.36 
                                       			
                                     | 
                                    
                                          
                                       			
                                        Cooling 
                                       			
                                     | 
                                    
                                          
                                       			
                                        12,028.36 
                                       			
                                     | 
                                 
                                 
                                       | 
                                          
                                       			
                                        3 
                                       			
                                     | 
                                    
                                          
                                       			
                                        6,601.13 
                                       			
                                     | 
                                    
                                          
                                       			
                                        7,042.22 
                                       			
                                     | 
                                    
                                          
                                       			
                                        Cooling 
                                       			
                                     | 
                                    
                                          
                                       			
                                        7,042.22 
                                       			
                                     | 
                                 
                              
                           
 
                        
                      
                      
                     최대부하의 비율로만 누계 축열량 검토를 수행할 경우, 장비용량 산정기준은 최대부하의 난방 60%, 냉방 50%로 나타났으며, 실제 지열원 히트펌프의
                     선정, 보일러 및 냉동기 선정을 수행할 경우 계산결과보다 더 높은 용량으로 열원장비가 산정되어 축열조에서 공급되는 최대열량과 장비용량의 차가 크게
                     나타나는 경우가 발생하였다. 이러한 경우 차이가 크게 나타난 장비에 한해 장비의 용량을 1단계 낮추어 재선정하고, 누계 축열량 검토를 재수행하여 장비선정의
                     적합성을 검토하였다.
                     
                     
 
                     TH-US 모델은 증기보일러를 적용한 것으로, 증기보일러에서 발생되는 증기로부터 필요한 에너지를 열교환하기 때문에 보일러의 용량은 적합하게 선정된
                     것으로 나타났으며, 냉동기의 용량이 변화하였다. 장비 선정시 지열원 히트펌프가 최대부하의 70% 보다 높게 산출되어 냉동기의 용량이 Zone 1~2의
                     경우 1단계 감소하였다.
                     
                     
 
                   
                  
                        3.3.4 CP-NS 모델
                      
Fig. 3은 CP-NS 모델의 개요를 나타낸 것이다. 모델에 적용된 지열원 히트펌프는 난방시 45℃의 온수를, 냉방시 7℃의 냉수를 생성하여 부하측으로 공급한다.
                     소형열병합발전기에서 발생되는 열매체는 자켓 냉각수로 사용된 온수(약 92~93℃)와 수증기를 포함한 증기형태의 배기가스가 있다. 이러한 열매체가 가진
                     열량을 부하측에서 이용하기 위해 상태가 다른 2종류의 유체를 열교환기 등을 통해 동일한 상태로 변환하고, 이때 변환하는 유체는 물의 형태로 변환하도록
                     계획하였다.
                     
                     
 
                     
                           Fig. 3. Overview of CP-NS model.
 
                      
                     난방시 소형열병합발전기에서 발생한 배기가스는 열교환기를 통해 온수로 열전달하고, 자켓 냉각수로 사용된 온수와 혼합하여 다시 열교환기로 이동, 지열원
                     히트펌프 발생온수의 온도와 동일한 45℃로 온도를 강하하여 부하측으로 공급하도록 계획하였다. 또한 냉방시에는 난방시와 유사한 방법으로, 소형열병합발전기에서
                     발생한 배기가스의 열교환 후 자켓 냉각수와 혼합한 온수(약 92∼93℃)를 중온수흡수식냉동기로 공급하여 냉수를 생성하여 부하측으로 공급하도록 하였다.
                     CP-NS 모델의 지열원 히트펌프는 TH-NS 모델군과 동일한 방법으로 장비를 선정하였다.
                     
                     
 
Table 11은 소형열병합발전기 및 중온수흡수식냉동기의 용량 산정결과를 나타낸 것으로, 지열원 히트펌프의 용량을 기준으로 최대부하를 만족하도록 계획하였다. 
                     
                     
 
                     
                           Table 11. Cogeneration plant and chiller specification of CP-NS
                         
                           
                                 
                                    
                                       | 
                                          
                                       			
                                        Zone 
                                       			
                                     | 
                                    
                                          
                                       			
                                        Small-scale cogeneration plant 
                                       			
                                     | 
                                    
                                          
                                       			
                                        Absorption chiller 
                                       			
                                     | 
                                 
                                 
                                       | 
                                          
                                       			
                                        Heating load 
                                       			
                                     | 
                                    
                                          
                                       			
                                        GSHP capacity 
                                       			
                                     | 
                                    
                                          
                                       			
                                        Capacity 
                                       			
                                     | 
                                    
                                          
                                       			
                                        Cooling load 
                                       			
                                     | 
                                    
                                          
                                       			
                                        GSHP capacity 
                                       			
                                     | 
                                    
                                          
                                       			
                                        Capacity 
                                       			
                                     | 
                                 
                                 
                                       | 
                                          
                                       			
                                        kW 
                                       			
                                     | 
                                    
                                          
                                       			
                                        kW 
                                       			
                                     | 
                                    
                                          
                                       			
                                        kW 
                                       			
                                     | 
                                    
                                          
                                       			
                                        USRT 
                                       			
                                     | 
                                    
                                          
                                       			
                                        USRT 
                                       			
                                     | 
                                    
                                          
                                       			
                                        USRT 
                                       			
                                     | 
                                 
                              
                              
                                    
                                       | 
                                          
                                       			
                                        1 
                                       			
                                     | 
                                    
                                          
                                       			
                                        2,627.9 
                                       			
                                     | 
                                    
                                          
                                       			
                                        880.5 
                                       			
                                     | 
                                    
                                          
                                       			
                                        1,747.4 
                                       			
                                     | 
                                    
                                          
                                       			
                                        686.4 
                                       			
                                     | 
                                    
                                          
                                       			
                                        259.5 
                                       			
                                     | 
                                    
                                          
                                       			
                                        426.9 
                                       			
                                     | 
                                 
                                 
                                       | 
                                          
                                       			
                                        2 
                                       			
                                     | 
                                    
                                          
                                       			
                                        2,354.7 
                                       			
                                     | 
                                    
                                          
                                       			
                                        880.5 
                                       			
                                     | 
                                    
                                          
                                       			
                                        1,474.2 
                                       			
                                     | 
                                    
                                          
                                       			
                                        615.0 
                                       			
                                     | 
                                    
                                          
                                       			
                                        259.5 
                                       			
                                     | 
                                    
                                          
                                       			
                                        355.5 
                                       			
                                     | 
                                 
                                 
                                       | 
                                          
                                       			
                                        3 
                                       			
                                     | 
                                    
                                          
                                       			
                                        1,435.0 
                                       			
                                     | 
                                    
                                          
                                       			
                                        528.3 
                                       			
                                     | 
                                    
                                          
                                       			
                                        906.7 
                                       			
                                     | 
                                    
                                          
                                       			
                                        374.8 
                                       			
                                     | 
                                    
                                          
                                       			
                                        155.7 
                                       			
                                     | 
                                    
                                          
                                       			
                                        219.1 
                                       			
                                     | 
                                 
                              
                           
 
                        
                      
                      
                     소형열병합발전기의 특성상 효율성, 유지관리성 향상과 운영비 절감을 위해서는 24시간 내내 지속적인 가동으로 가동이 중단되는 일이 없도록 계획하여야
                     한다. 이를 위해 지열원 히트펌프가 아닌 소형열병합발전기가 주열원으로 적용하여 24시간 내내 가동하도록 계획하였고, 소형열병합발전기 생산 열량의 초과열량이
                     부하로 발생할 때, 지열원 히트펌프가 추가로 가동하여 열량을 공급하도록 계획하였다.
                     
                     
 
                     소형열병합발전기는 시간대별 부하율이 최소일 때, 50%의 부분부하 운전에서 부하측에서 필요로 하는 열량을 공급할 수 있도록 계획하였다. 이는 시간대별
                     부하율이 변화하여도 소형열병합발전기의 효율을 유지하기 위한 것으로, 장비의 효율저하가 일어나지 않는 최소 부분부하에서의 운전이 부하측에서 필요로 하는
                     열량을 만족하도록 계획한 것이다. 상세 시스템 운영계획으로는, 시간대별 부하율이 최소가 되어도 소형열병합기의 효율은 큰 저하 없이 유지가 되며, 시간대별
                     부하율이 상승하면 소형열병합발전기의 가동율이 상승, 시간대별 부하율 상승으로 인한 부족한 열량은 지열원 히트펌프가 추가로 공급하도록 계획하였다.
                     
                     
 
                     또한 배기가스의 열량을 이용하기 위해 열교환기를 계획하여 자켓 냉각수와 동일한 온도의 온수로 열교환하도록 계획하였으며, 배기가스의 온도는 약 150℃로
                     천연가스 사용시 130℃까지 냉각하여 이 열을 이용할 수 있다.
                     
                     
 
                     배기가스 열교환기의 2차측(온수)의 입․출구온도는 소형열병합발전기 자켓 냉각수의 온도조건인 93℃, 80℃로 결정하였다. 이는 중온수흡수식냉동기의
                     온수 조건과도 동일하여, 이를 이용할 수 있다.
                     
                     
 
                   
                
               
                     3.4 초기투자비용 비교
                   
                  초기투자비용 검토는 가상단지를 대상으로 중앙 냉난방시스템을 평가한 것으로, 상세한 초기투자비용은 차후에 산정하는 것으로 하며, 본 연구에 필요한 최소금액을
                  기준으로 초기투자비용을 산출하였고 각 모델별 초기투자비용 산정 내용은 
Table 12~
Table 14와 같다. 실제 시공 도면과 지중 특성에 따라 달라지는 천공비용 및 지중열교환기 매설비용 등은 공사비와 관련된 부분으로 실제 시공시에만 정확한 산출이
                  가능하기 때문에 제외하였다. 이에 모델별 개략적인 장비변화에 따른 변화에만 참조할 수 있을 것으로 판단된다. 
                  
                  
 
                  
                        Table 12. Initial investment cost of TH-NS(Korean Won)
                      
                        
                              
                                 
                                    | 
                                       
                                    			
                                     Classification 
                                    			
                                  | 
                                 
                                       
                                    			
                                     Capacity 
                                    			
                                  | 
                                 
                                       
                                    			
                                     Amount 
                                    			
                                  | 
                                 
                                       
                                    			
                                     Unit cost 
                                    			
                                  | 
                                 
                                       
                                    			
                                     Total cost 
                                    			
                                  | 
                              
                           
                           
                                 
                                    | 
                                       
                                    			
                                     Ground source heat pump 
                                    			
                                  | 
                                 
                                       
                                    			
                                     50 
                                    			
                                  | 
                                 
                                       
                                    			
                                     USRT 
                                    			
                                  | 
                                 
                                       
                                    			
                                     27 
                                    			
                                  | 
                                 
                                       
                                    			
                                     40,500,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     1,093,500,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Ground source deep-well pump 
                                    			
                                  | 
                                 
                                       
                                    			
                                     285 
                                    			
                                  | 
                                 
                                       
                                    			
                                     ℓ/min 
                                    			
                                  | 
                                 
                                       
                                    			
                                     60 
                                    			
                                  | 
                                 
                                       
                                    			
                                     2,450,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     147,000,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Ground source circulation pump 
                                    			
                                  | 
                                 
                                       
                                    			
                                     - 
                                    			
                                  | 
                                 
                                       
                                    			
                                     - 
                                    			
                                  | 
                                 
                                       
                                    			
                                     9 
                                    			
                                  | 
                                 
                                       
                                    			
                                     5,000,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     45,000,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Cold charge pump 
                                    			
                                  | 
                                 
                                       
                                    			
                                     - 
                                    			
                                  | 
                                 
                                       
                                    			
                                     - 
                                    			
                                  | 
                                 
                                       
                                    			
                                     9 
                                    			
                                  | 
                                 
                                       
                                    			
                                     5,000,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     45,000,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Cold discharge pump 
                                    			
                                  | 
                                 
                                       
                                    			
                                     - 
                                    			
                                  | 
                                 
                                       
                                    			
                                     - 
                                    			
                                  | 
                                 
                                       
                                    			
                                     9 
                                    			
                                  | 
                                 
                                       
                                    			
                                     5,000,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     45,000,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Plate heat exchanger 
                                    			
                                  | 
                                 
                                       
                                    			
                                     - 
                                    			
                                  | 
                                 
                                       
                                    			
                                     - 
                                    			
                                  | 
                                 
                                       
                                    			
                                     3 
                                    			
                                  | 
                                 
                                       
                                    			
                                     100,000,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     300,000,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Closed type expansion tank 
                                    			
                                  | 
                                 
                                       
                                    			
                                     100 
                                    			
                                  | 
                                 
                                       
                                    			
                                     ℓ 
                                    			
                                  | 
                                 
                                       
                                    			
                                     3 
                                    			
                                  | 
                                 
                                       
                                    			
                                     1,200,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     3,600,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Hot water boiler 
                                    			
                                  | 
                                 
                                       
                                    			
                                     930 
                                    			
                                  | 
                                 
                                       
                                    			
                                     kW 
                                    			
                                  | 
                                 
                                       
                                    			
                                     4 
                                    			
                                  | 
                                 
                                       
                                    			
                                     65,700,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     262,800,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Hot water boiler 
                                    			
                                  | 
                                 
                                       
                                    			
                                     465 
                                    			
                                  | 
                                 
                                       
                                    			
                                     kW 
                                    			
                                  | 
                                 
                                       
                                    			
                                     2 
                                    			
                                  | 
                                 
                                       
                                    			
                                     49,500,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     99,000,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Heat exchanger 
                                    			
                                  | 
                                 
                                       
                                    			
                                     308 
                                    			
                                  | 
                                 
                                       
                                    			
                                     kg/h 
                                    			
                                  | 
                                 
                                       
                                    			
                                     1 
                                    			
                                  | 
                                 
                                       
                                    			
                                     16,755,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     16,755,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Heat exchanger 
                                    			
                                  | 
                                 
                                       
                                    			
                                     261 
                                    			
                                  | 
                                 
                                       
                                    			
                                     kg/h 
                                    			
                                  | 
                                 
                                       
                                    			
                                     1 
                                    			
                                  | 
                                 
                                       
                                    			
                                     15,145,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     15,145,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Heat exchanger 
                                    			
                                  | 
                                 
                                       
                                    			
                                     160 
                                    			
                                  | 
                                 
                                       
                                    			
                                     kg/h 
                                    			
                                  | 
                                 
                                       
                                    			
                                     1 
                                    			
                                  | 
                                 
                                       
                                    			
                                     12,155,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     12,155,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Screw chiller 
                                    			
                                  | 
                                 
                                       
                                    			
                                     240 
                                    			
                                  | 
                                 
                                       
                                    			
                                     USRT 
                                    			
                                  | 
                                 
                                       
                                    			
                                     2 
                                    			
                                  | 
                                 
                                       
                                    			
                                     105,900,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     211,800,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Screw chiller 
                                    			
                                  | 
                                 
                                       
                                    			
                                     200 
                                    			
                                  | 
                                 
                                       
                                    			
                                     USRT 
                                    			
                                  | 
                                 
                                       
                                    			
                                     2 
                                    			
                                  | 
                                 
                                       
                                    			
                                     90,200,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     180,400,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Screw chiller 
                                    			
                                  | 
                                 
                                       
                                    			
                                     120 
                                    			
                                  | 
                                 
                                       
                                    			
                                     USRT 
                                    			
                                  | 
                                 
                                       
                                    			
                                     2 
                                    			
                                  | 
                                 
                                       
                                    			
                                     55,300,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     110,600,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Cooling tower 
                                    			
                                  | 
                                 
                                       
                                    			
                                     250 
                                    			
                                  | 
                                 
                                       
                                    			
                                     CRT 
                                    			
                                  | 
                                 
                                       
                                    			
                                     2 
                                    			
                                  | 
                                 
                                       
                                    			
                                     16,600,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     33,200,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Cooling tower 
                                    			
                                  | 
                                 
                                       
                                    			
                                     225 
                                    			
                                  | 
                                 
                                       
                                    			
                                     CRT 
                                    			
                                  | 
                                 
                                       
                                    			
                                     2 
                                    			
                                  | 
                                 
                                       
                                    			
                                     16,500,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     33,000,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Cooling tower 
                                    			
                                  | 
                                 
                                       
                                    			
                                     150 
                                    			
                                  | 
                                 
                                       
                                    			
                                     CRT 
                                    			
                                  | 
                                 
                                       
                                    			
                                     2 
                                    			
                                  | 
                                 
                                       
                                    			
                                     13,300,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     26,600,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Total 
                                    			
                                  | 
                                 
                                       
                                    			
                                       
                                    			
                                  | 
                                 
                                       
                                    			
                                       
                                    			
                                  | 
                                 
                                       
                                    			
                                       
                                    			
                                  | 
                                 
                                       
                                    			
                                     2,680,555,000 
                                    			
                                  | 
                              
                           
                        
 
                     
                   
                   
                  
                        Table 13. Initial investment cost of TH-US(Korean Won)
                      
                        
                              
                                 
                                    | 
                                       
                                    			
                                     Classification 
                                    			
                                  | 
                                 
                                       
                                    			
                                     Capacity 
                                    			
                                  | 
                                 
                                       
                                    			
                                     Amount 
                                    			
                                  | 
                                 
                                       
                                    			
                                     Unit cost 
                                    			
                                  | 
                                 
                                       
                                    			
                                     Total cost 
                                    			
                                  | 
                              
                           
                           
                                 
                                    | 
                                       
                                    			
                                     Ground source heat pump 
                                    			
                                  | 
                                 
                                       
                                    			
                                     50 
                                    			
                                  | 
                                 
                                       
                                    			
                                     USRT 
                                    			
                                  | 
                                 
                                       
                                    			
                                     27 
                                    			
                                  | 
                                 
                                       
                                    			
                                     40,500,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     1,093,500,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Ground source deep-well pump 
                                    			
                                  | 
                                 
                                       
                                    			
                                     285 
                                    			
                                  | 
                                 
                                       
                                    			
                                     ℓ/min 
                                    			
                                  | 
                                 
                                       
                                    			
                                     60 
                                    			
                                  | 
                                 
                                       
                                    			
                                     2,450,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     147,000,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Ground source circulation pump 
                                    			
                                  | 
                                 
                                       
                                    			
                                     - 
                                    			
                                  | 
                                 
                                       
                                    			
                                     - 
                                    			
                                  | 
                                 
                                       
                                    			
                                     9 
                                    			
                                  | 
                                 
                                       
                                    			
                                     5,000,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     45,000,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Cold charge pump 
                                    			
                                  | 
                                 
                                       
                                    			
                                     - 
                                    			
                                  | 
                                 
                                       
                                    			
                                     - 
                                    			
                                  | 
                                 
                                       
                                    			
                                     9 
                                    			
                                  | 
                                 
                                       
                                    			
                                     5,000,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     45,000,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Cold discharge pump 
                                    			
                                  | 
                                 
                                       
                                    			
                                     - 
                                    			
                                  | 
                                 
                                       
                                    			
                                     - 
                                    			
                                  | 
                                 
                                       
                                    			
                                     9 
                                    			
                                  | 
                                 
                                       
                                    			
                                     5,000,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     45,000,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Plate heat exchanger 
                                    			
                                  | 
                                 
                                       
                                    			
                                     - 
                                    			
                                  | 
                                 
                                       
                                    			
                                     - 
                                    			
                                  | 
                                 
                                       
                                    			
                                     3 
                                    			
                                  | 
                                 
                                       
                                    			
                                     100,000,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     300,000,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Closed type expansion tank 
                                    			
                                  | 
                                 
                                       
                                    			
                                     100 
                                    			
                                  | 
                                 
                                       
                                    			
                                     ℓ 
                                    			
                                  | 
                                 
                                       
                                    			
                                     3 
                                    			
                                  | 
                                 
                                       
                                    			
                                     1,200,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     3,600,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Hot water boiler 
                                    			
                                  | 
                                 
                                       
                                    			
                                     930 
                                    			
                                  | 
                                 
                                       
                                    			
                                     kW 
                                    			
                                  | 
                                 
                                       
                                    			
                                     4 
                                    			
                                  | 
                                 
                                       
                                    			
                                     65,700,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     262,800,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Hot water boiler 
                                    			
                                  | 
                                 
                                       
                                    			
                                     465 
                                    			
                                  | 
                                 
                                       
                                    			
                                     kW 
                                    			
                                  | 
                                 
                                       
                                    			
                                     2 
                                    			
                                  | 
                                 
                                       
                                    			
                                     49,500,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     99,000,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Heat exchanger 
                                    			
                                  | 
                                 
                                       
                                    			
                                     271 
                                    			
                                  | 
                                 
                                       
                                    			
                                     kg/h 
                                    			
                                  | 
                                 
                                       
                                    			
                                     1 
                                    			
                                  | 
                                 
                                       
                                    			
                                     15,605,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     15,605,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Heat exchanger 
                                    			
                                  | 
                                 
                                       
                                    			
                                     243 
                                    			
                                  | 
                                 
                                       
                                    			
                                     kg/h 
                                    			
                                  | 
                                 
                                       
                                    			
                                     1 
                                    			
                                  | 
                                 
                                       
                                    			
                                     14,685,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     14,685,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Heat exchanger 
                                    			
                                  | 
                                 
                                       
                                    			
                                     148 
                                    			
                                  | 
                                 
                                       
                                    			
                                     kg/h 
                                    			
                                  | 
                                 
                                       
                                    			
                                     1 
                                    			
                                  | 
                                 
                                       
                                    			
                                     11,695,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     11,695,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Screw chiller 
                                    			
                                  | 
                                 
                                       
                                    			
                                     150 
                                    			
                                  | 
                                 
                                       
                                    			
                                     USRT 
                                    			
                                  | 
                                 
                                       
                                    			
                                     4 
                                    			
                                  | 
                                 
                                       
                                    			
                                     66,700,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     266,800,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Screw chiller 
                                    			
                                  | 
                                 
                                       
                                    			
                                     100 
                                    			
                                  | 
                                 
                                       
                                    			
                                     USRT 
                                    			
                                  | 
                                 
                                       
                                    			
                                     2 
                                    			
                                  | 
                                 
                                       
                                    			
                                     48,200,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     96,400,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Cooling tower 
                                    			
                                  | 
                                 
                                       
                                    			
                                     175 
                                    			
                                  | 
                                 
                                       
                                    			
                                     CRT 
                                    			
                                  | 
                                 
                                       
                                    			
                                     4 
                                    			
                                  | 
                                 
                                       
                                    			
                                     13,600,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     54,400,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Cooling tower 
                                    			
                                  | 
                                 
                                       
                                    			
                                     125 
                                    			
                                  | 
                                 
                                       
                                    			
                                     CRT 
                                    			
                                  | 
                                 
                                       
                                    			
                                     2 
                                    			
                                  | 
                                 
                                       
                                    			
                                     12,300,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     24,600,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Hot water storage 
                                    			
                                  | 
                                 
                                       
                                    			
                                     14,120 
                                    			
                                  | 
                                 
                                       
                                    			
                                     USRT․h 
                                    			
                                  | 
                                 
                                       
                                    			
                                     1USRT․h 
                                    			
                                  | 
                                 
                                       
                                    			
                                     590,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     8,330,800,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Total 
                                    			
                                  | 
                                 
                                       
                                    			
                                       
                                    			
                                  | 
                                 
                                       
                                    			
                                       
                                    			
                                  | 
                                 
                                       
                                    			
                                       
                                    			
                                  | 
                                 
                                       
                                    			
                                     10,855,885,000 
                                    			
                                  | 
                              
                           
                        
 
                     
                   
                   
                  
                        Table 14. Initial investment cost of CP-NS(Korean Won)
                      
                        
                              
                                 
                                    | 
                                       
                                    			
                                     Classification 
                                    			
                                  | 
                                 
                                       
                                    			
                                     Capacity 
                                    			
                                  | 
                                 
                                       
                                    			
                                     Amount 
                                    			
                                  | 
                                 
                                       
                                    			
                                     Unit cost 
                                    			
                                  | 
                                 
                                       
                                    			
                                     Total cost 
                                    			
                                  | 
                              
                           
                           
                                 
                                    | 
                                       
                                    			
                                     Ground source heat pump 
                                    			
                                  | 
                                 
                                       
                                    			
                                     50 
                                    			
                                  | 
                                 
                                       
                                    			
                                     USRT 
                                    			
                                  | 
                                 
                                       
                                    			
                                     27 
                                    			
                                  | 
                                 
                                       
                                    			
                                     40,500,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     1,093,500,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Ground source deep-well pump 
                                    			
                                  | 
                                 
                                       
                                    			
                                     285 
                                    			
                                  | 
                                 
                                       
                                    			
                                     ℓ/min 
                                    			
                                  | 
                                 
                                       
                                    			
                                     60 
                                    			
                                  | 
                                 
                                       
                                    			
                                     2,450,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     147,000,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Ground source circulation pump 
                                    			
                                  | 
                                 
                                       
                                    			
                                     - 
                                    			
                                  | 
                                 
                                       
                                    			
                                     - 
                                    			
                                  | 
                                 
                                       
                                    			
                                     9 
                                    			
                                  | 
                                 
                                       
                                    			
                                     5,000,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     45,000,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Cold charge pump 
                                    			
                                  | 
                                 
                                       
                                    			
                                     - 
                                    			
                                  | 
                                 
                                       
                                    			
                                     - 
                                    			
                                  | 
                                 
                                       
                                    			
                                     9 
                                    			
                                  | 
                                 
                                       
                                    			
                                     5,000,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     45,000,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Cold discharge pump 
                                    			
                                  | 
                                 
                                       
                                    			
                                     - 
                                    			
                                  | 
                                 
                                       
                                    			
                                     - 
                                    			
                                  | 
                                 
                                       
                                    			
                                     9 
                                    			
                                  | 
                                 
                                       
                                    			
                                     5,000,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     45,000,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Plate heat exchanger 
                                    			
                                  | 
                                 
                                       
                                    			
                                     - 
                                    			
                                  | 
                                 
                                       
                                    			
                                     - 
                                    			
                                  | 
                                 
                                       
                                    			
                                     3 
                                    			
                                  | 
                                 
                                       
                                    			
                                     100,000,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     300,000,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Closed type expansion tank 
                                    			
                                  | 
                                 
                                       
                                    			
                                     100 
                                    			
                                  | 
                                 
                                       
                                    			
                                     ℓ 
                                    			
                                  | 
                                 
                                       
                                    			
                                     3 
                                    			
                                  | 
                                 
                                       
                                    			
                                     1,200,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     3,600,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Heat exchanger(Exhaust gas) 
                                    			
                                  | 
                                 
                                       
                                    			
                                     57.4 
                                    			
                                  | 
                                 
                                       
                                    			
                                     kg/h 
                                    			
                                  | 
                                 
                                       
                                    			
                                     2 
                                    			
                                  | 
                                 
                                       
                                    			
                                     5,800,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     11,600,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Heat exchanger(Exhaust gas) 
                                    			
                                  | 
                                 
                                       
                                    			
                                     45.0 
                                    			
                                  | 
                                 
                                       
                                    			
                                     kg/h 
                                    			
                                  | 
                                 
                                       
                                    			
                                     1 
                                    			
                                  | 
                                 
                                       
                                    			
                                     4,900,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     4,900,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Heat exchanger 
                                    			
                                  | 
                                 
                                       
                                    			
                                     271.2 
                                    			
                                  | 
                                 
                                       
                                    			
                                     kg/h 
                                    			
                                  | 
                                 
                                       
                                    			
                                     1 
                                    			
                                  | 
                                 
                                       
                                    			
                                     15,605,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     15,605,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Heat exchanger 
                                    			
                                  | 
                                 
                                       
                                    			
                                     243.0 
                                    			
                                  | 
                                 
                                       
                                    			
                                     kg/h 
                                    			
                                  | 
                                 
                                       
                                    			
                                     1 
                                    			
                                  | 
                                 
                                       
                                    			
                                     14,685,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     14,685,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Heat exchanger 
                                    			
                                  | 
                                 
                                       
                                    			
                                     148.1 
                                    			
                                  | 
                                 
                                       
                                    			
                                     kg/h 
                                    			
                                  | 
                                 
                                       
                                    			
                                     1 
                                    			
                                  | 
                                 
                                       
                                    			
                                     11,695,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     11,695,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Hot water driven absorption chiller 
                                    			
                                  | 
                                 
                                       
                                    			
                                     210 
                                    			
                                  | 
                                 
                                       
                                    			
                                     USRT 
                                    			
                                  | 
                                 
                                       
                                    			
                                     4 
                                    			
                                  | 
                                 
                                       
                                    			
                                     74,480,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     297,920,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Hot water driven absorption chiller 
                                    			
                                  | 
                                 
                                       
                                    			
                                     120 
                                    			
                                  | 
                                 
                                       
                                    			
                                     USRT 
                                    			
                                  | 
                                 
                                       
                                    			
                                     2 
                                    			
                                  | 
                                 
                                       
                                    			
                                     52,700,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     105,400,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Cooling tower 
                                    			
                                  | 
                                 
                                       
                                    			
                                     450 
                                    			
                                  | 
                                 
                                       
                                    			
                                     CRT 
                                    			
                                  | 
                                 
                                       
                                    			
                                     4 
                                    			
                                  | 
                                 
                                       
                                    			
                                     66,490,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     265,960,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Cooling tower 
                                    			
                                  | 
                                 
                                       
                                    			
                                     300 
                                    			
                                  | 
                                 
                                       
                                    			
                                     CRT 
                                    			
                                  | 
                                 
                                       
                                    			
                                     2 
                                    			
                                  | 
                                 
                                       
                                    			
                                     50,400,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     100,800,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Small-scale cogeneration plant 
                                    			
                                  | 
                                 
                                       
                                    			
                                     1 
                                    			
                                  | 
                                 
                                       
                                    			
                                     kW 
                                    			
                                  | 
                                 
                                       
                                    			
                                     4,308 kW 
                                    			
                                  | 
                                 
                                       
                                    			
                                     3,373,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     14,530,884,000 
                                    			
                                  | 
                              
                              
                                    | 
                                       
                                    			
                                     Total 
                                    			
                                  | 
                                 
                                       
                                    			
                                       
                                    			
                                  | 
                                 
                                       
                                    			
                                       
                                    			
                                  | 
                                 
                                       
                                    			
                                       
                                    			
                                  | 
                                 
                                       
                                    			
                                     17,038,549,000 
                                    			
                                  | 
                              
                           
                        
 
                     
                   
                   
Table 15의 내용 결과와 같이 TH-NS 초기투자비용을 보면 TH-US 모델과 CP-NS 모델에 비해 현저히 낮은 초기투자비를 나타내고 있다. 시스템이 가장
                  단순한 TH-NS 모델이 초기투자비가 가장 낮기 때문에 공동주택에 중앙 냉난방시스템 적용에 가장 유리함을 알 수 있으며, 축열조가 없는 시스템으로
                  기계실 공간확보에 유리하고 유지관리 측면에서도 타 모델에 비해 상대적으로 유리하다.
                  
                  
 
                  
                        Table 15. Initial investment cost of each model
                      
                        
                              
                                 
                                    | 
                                       
                                    			
                                     TH-NS 
                                    			
                                  | 
                                 
                                       
                                    			
                                     TH-US 
                                    			
                                  | 
                                 
                                       
                                    			
                                     CP-NS 
                                    			
                                  | 
                              
                           
                           
                                 
                                    | 
                                       
                                    			
                                     ₩ 2,680,555,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     ₩ 10,855,885,000 
                                    			
                                  | 
                                 
                                       
                                    			
                                     ₩ 17,038,549,000 
                                    			
                                  | 
                              
                           
                        
 
                     
                   
                   
                  TH-US 모델은 TH-NS 모델에 비해 축열조 설치비용이 과다하게 발생하였고, 이로 인해 TH-NS 모델의 초기투자비용 차이가 약 4~5배 가량으로
                  나타났다. 실제 시스템 운영을 통해 이를 절감한다고 하여도, 초기투자비용의 회수가 가능할지에 대한 우려가 있으며, 일반 업무용 건물의 경우 축열조를
                  적용한 경우 주간시간 동안 냉동기의 가동이 거의 발생하지 않아 운영비에 의한 절감이 크지만, 공동주택에 적용할 경우 주간시간에도 냉동기가 가동되어
                  결국 발생하는 에너지비용이 비축열 방식과 큰 차이가 없을 것으로 예상된다. 다만, 비축열 방식은 최대부하의 약 65%의 비율로 장비를 선정하여 축열
                  방식에 비해 장비 크기가 크고, 이로 인해 소비되는 에너지의 양이 많기에 정확한 유지관리 및 운영비 비교가 추가적으로 필요할 것으로 판단된다. 
                  
                  
 
                  CP-NS 모델은 소형열병합발전기를 적용한 모델로 TH 모델군에 비해 초기투자비가 과도하게 발생하였으며, 생산되는 전기의 가격을 감안한다 해도 경제성이
                  확보되지 않을 것이라 예상된다. 또한 TH 모델군과 다르게, 소형열병합발전기는 1년 365일 내내 작동을 하며, 이 때 소비되는 연료인 천연가스의
                  금액과 생산되는 전력을 비교하여도 비효율적인 시스템이라 판단되어 공동주택의 중앙 냉난방시스템으로는 적합하지 않다고 판단된다.
                  
                  
 
                
             
            
                  4. 결 론
                
               본 연구는 공동주택을 대상으로 중앙 냉난방시스템을 적용하기 위한 기계설비 분야의 적용방안, 고려사항 등을 검토하여 적용 가능한 시스템을 3개 선정하고,
               선정된 시스템의 초기투자비에 대한 경제성 분석을 수행하여 보았다. 
               
               
 
               공동주택의 사용패턴을 검토해보았을 때, 공동주택 중앙 냉난방시스템으로 적용 가능한 모델을 3가지로 구분하여 선정할 수 있었으며 각 모델의 초기투자비용
               비교 및 결론은 다음과 같다.
               
               
 
               (1) 비축열방식은 축열방식에 비해 지열원 히트펌프를 제외한 열원설비의 용량이 다소 증가하는 것으로 나타났지만, 실제 장비 용량에 따른 규격이 세분화되지
               않아 큰 차이가 발생하지 않았다. 또한 장비의 초기투자비용 또한 큰 차이가 발생하지 않았으며, 설비 및 배관 등의 단순화와 유지관리성을 위해서는 비축열
               방식이 유리한 것으로 판단된다.
               
               
 
               (2) 축열방식을 적용할 경우 24시간 동안 부하가 발생하는 공동주택의 특성으로 인해 비축열방식에 비해 다소 불리한 것으로 판단되며, 초기투자비 또한
               과다하게 발생하여 경제성 측면에서 불리한 것으로 판단된다.
               
               
 
               (3) 일반적으로 축열방식은 업무시설 등과 같이 건물의 운영시간과 비운영시간이 구분되고, 비운영시간에 저렴한 심야전기 등을 이용하여 열을 저장하여
               주간에 사용하는 것으로, 24시간 동안 부하가 발생하는 공동주택의 경우 축열이 제대로 이루어지지 않으며, 이렇게 저장한 열로 주간부하를 감당할 수
               없어 장비의 연속적인 운전으로 수명의 감소, 효율의 저하 등의 문제점이 발생할 것으로 판단된다.
               
               
 
               (4) 소형열병합발전기의 경우, 초기공사비에 비해 열적인 측면에서의 기대효과는 미미하였으며, 전력 생산으로 인한 운영비, 전기 사용요금에 대한 부분이
               추가적으로 검토되어야 할 것으로 판단된다. 또한, 기계실 면적의 상승으로 인한 주차장 등의 면적 감소, 외기량 확보를 위한 환기탑 계획, 기존 시스템에
               비해 복잡한 배관 등으로 인해 시스템의 적용성은 다소 낮은 것으로 평가되었다.
               
 
               본 연구에서는 초기투자비를 통한 시스템 비교검토를 수행하였지만, 경제성에 대한 검토는 초기투자비 외에도 유지관리비용 및 운영비에 대한 LCC 검토가
               수반되어야 보다 신뢰성 있는 경제성 검토가 될 수 있다. 따라서 추후 해당 중앙 냉난방시스템 검토 모델에 대한 LCC 분석을 토대로 보다 정확한 경제성
               평가를 수행할 예정이며, 소형열병합발전기의 경우 전력 생산에 대한 사용계획 및 발전량 등을 추가 검토하여 소형열병합발전기를 이용한 중앙 냉난방시스템
               적용성에 대한 정밀 분석이 필요할 것으로 예상된다.