Title |
Analysis of Voltage Drop Characteristics of Transformer-based 3-phase Voltage Disturbance Generator |
Authors |
Heung-Soo Han ; 李Young-Ho Lee ; Woong-Hyub Song ; 魯Eui-Cheol Nho ; In-Dong Kim ; Heung-Geun Kim ; Tae-Won Chun |
DOI |
10.6113/TKPE/2010.15.5.411 |
Keywords |
Voltage disturbance generator; Series transformer; Voltage drop |
Abstract |
A voltage drop characteristics of a transformer-based voltage disturbance generator with series transformers is analysed. It is well known that a voltage disturbance generator with series transformer is cost-effective and reliable compared with other types. The voltage drop depends on the %Z of the transformer, power rating, and output power factor. A wrong design of the transformer results in a severe voltage drop, which can not guarantee the proper performance of the generator. The voltage drop is analysed under the condition of 10kVA output power rating and 4% of %Z with the variation of power factor. It is found through simulations and experiments that the drop increases as the power factor decreases in lagging mode, and the drop is 4% of the rated voltage in case of 0.85 lagging power factor. |