Title Effect of Installation of Ventilation Systems and air Cleaning Units in Daycare Center on Particulate Matter Reduction Using Simulation
Authors Seung Hwan Park ; So Woo Park ; Doo Sam Song
DOI https://doi.org/10.6110/KJACR.2021.33.7.359
Page pp.359-368
ISSN 1229-6422
Keywords 초미세먼지; 환기시스템; 공기청정기; 활동도; 어린이집; 외기 미세먼지 농도 PM2.5; Ventilation system; Air cleaning unit; Activity; Daycare center; Outdoor PM2.5 concentration
Abstract The purpose of this study is to identify an effective method among solutions such as ventilation system and air cleaning unit operation as measures to reduce particulate matters in a child care center. Results are as follows. When children are active in the child-care room, the indoor PM2.5 concentration is increased up to 5.5 times compared to the Korean standard of 35 ㎍/㎥. PM2.5 concentrations in all child-care rooms exceeded the standard. In such situations, if the ventilation system was operated, indoor PM2.5 concentration could be maintained below the standard value except for child-care room 1 on the 1st floor. In case of an air cleaning unit with a capacity of CADR 57 ㎡, a filter efficiency of 80%, and an operation rate of 95%, it did not satisfy the standard value of indoor PM2.5 concentration for all child-care rooms. However, if the capacity of air cleaning unit was increased to CADR 87 ㎡ under the condition of 95% filter efficiency, indoor PM2.5 concentrations in all child-care rooms could be maintained below the standard value. Thus, if an air cleaning unit with a capacity of CADR 57 ㎡ and 95% filter efficiency is operated in combination with a ventilation system, indoor PM2.5 concentrations in child-care rooms can be maintained below the standard value.