Title A Study on Standard Weather Data in Pusan
Authors 김동완 ; 박민용 ; 김명진
Page pp.69-78
ISSN 12251674
Abstract To get Standard Weather Data in Pusan for dynamic Heat Load calculation and HVAC system simulation, the 8760 sequential hourly values for seven weather elements have been obtained from daily weather report recorded at Pusan local weather station for past 10 years(1981-1990).Applying the monthly average method developed by Japanese Society of Heating, Air-Conditioning and Sanitary Engineers,the standard year data have been selected from three main weather elements.(DBT, AH, I )The results are as followings:1. The Test Reference Year consisted of 12 months chosen from different calendar year has been determined.2. The Typical Weather Year which means a year close to a average value is the year of 1988 during 10-year-period.3. During the period, Winter Season needed the maximum heating load is from Dec. 1983 to Mar. 1984 and Summer Season needed the maximum cooling load is from Jun. 1990 to Sep. 1990