Title |
Evaluation of Applicability and Level of Illumination According to the Elapsed Year for Apartment underground Parking Garages |
DOI |
http://dx.doi.org/10.5659/JAIK_PD.2015.31.8.121 |
Keywords |
Elapsed Year ; Underground Parking Garages ; Standard of Illumination ; Applicability |
Abstract |
The purpose of this study is to evaluate the level of illumination and the process of applicability in its aspects of the legal practice. An object of investigation was used with the data which were obtained by the differences in buildings completed for apartment underground parking garage since the late 1990s. The sample size was that of 9 apartment houses in Ulsan. The results of this study were as follows; 1) Overall, the level of illuminance is shown to be kept below the criteria of the regulation. 2) In order to satisfy the criteria suggested of the law, subjects of the investigation don't have an active aspect to reflect the objectives and significance for changing standards. But are merely obsessed with meeting minimum requirements for illumination installation. 3) In the current situation where only minimum illumination is regulated, a problem occurs because improvement of uniformity ratio has not been made. So better regulations are needed to alleviate the problem of illumination that is need to adopt the regulations in the average illumination. |