Title Investigation of Dynamic Characteristcs Uninterruptible Power Supply System (UPS) Using Shaking Table Tests
Authors Seung-Jae Lee ; Joo-Young Kim ; Kyoung-Kyu Choi
DOI https://doi.org/10.5659/JAIK_SC.2019.35.11.129
Page pp.129-136
ISSN 1226-9107
Keywords UPS; shaking table test; non-structural elements; dynamic characteristics; natural frequency; damping ratio;acceleration time history response
Abstract Non-structural elements are vulnerable to earthquake ground motion. In this study, an experimental study for the electrical non-structural element was performed using tri-axial shaking table tests. A 100kVA UPS(Uninterruptible Power Supply system) was used as the test specimen. The test specimen was anchored to the concrete slab using the conventional installation detail. The input acceleration were generated in accordance with ICC-ES AC156 code. Scale factors of the input acceleration with respect to the required response spectrum defined in ICC-ES AC156 were from 25% to 600%. Based on the test results, damage and dynamic characteristics of UPS were evaluated and analyzed including natural frequency, damping ratio, acceleration time history response, dynamic amplification factor and relative displacement.