Title |
Analysis of Roof Load and Dynamic Characteristics of Traditional Timber Building Considering Column Axial Force and Ambient Vibration Measurement |
Authors |
김영민(Kim, Yeong-Min) ; 김윤미(Kim, Yoon-Mi) ; 김형준(Kim, Hyung-Jun) ; 하태욱(Ha, Tae-Uk) ; 신은미(Shin, Eun-Mi) ; 김원종(Kim, Won-Jong) |
DOI |
https://doi.org/10.5659/JAIK.2021.37.11.271 |
Keywords |
Traditional Timber Building; Roof Load; Column Axial Force; Ambient Vibration Measurement |
Abstract |
In this paper, filed measurement and structural analysis were performed syntagmatically to figure out structural characteristics of traditional
timber structure. Load cell was installed between column and foundation stone to measure column axial force, and ambient vibration test was
performed to measure natural vibration frequency and mode shape. The results of these two field measurements were compared and verified
by the 3-dimensional structural analysis results. From the axial force measurement and structural analysis, the roof load was estimated
4.763kN/m2, and this figure belongs to the general range of the traditional timber building. The roof loading pattern of 32 regions was
applied to the analysis model, it showed 98.36% accuracy for the measured column axial forces. From the comparison between ambient
vibration measurement and eigenvalue analysis, the relative rotational stiffness of the main structural members were evaluated to be 10~20%.
It turned out that the stiffness of walls should be considered in analyzing the traditional timber structure. |