Title |
Non-contact Screening Center of Infectious Diseases for Cross Infection Prevention |
Authors |
조진균(Cho, Jinkyun) ; 김진호(Kim, Jinho) |
DOI |
https://doi.org/10.5659/JAIK.2022.38.10.219 |
Keywords |
Infectious Disease; Screening Center; Ventilation System; Viral Aerosol; Cross Infection; CFD; Tracer Gas |
Abstract |
In this study, to fundamentally solve the risk of cross-infection in screening centers responding to infectious diseases, a new non-contact
screening center was developed that supplemented the problems of existing screening centers. Numerical analysis was performed on the
effectiveness of a ventilation system to remove viral aerosols and prevent cross-infection. Moreover, full-scale field measurements and SF6
tracer gas simulating viral aerosol was used under the same conditions as it was for the numerical analysis, comparison, and verification
when CFD simulations were performed. Currently, COVID-19 screening centers operating in Korea can be divided into five types; the risk of
cross-infection is very high due to its structure where the movement of medical staff and suspected patients cannot be separated. As a result
of the CFD simulation on the ventilation system of a non-contact screening center, among the 3,000 particles generated from a patient, not a
single particle was transmitted from the specimen collection booth to the adjacent examination room. More than 99% of the particles were
removed by the ventilation system after 559 seconds. As a result of the in-situ measurement, the concentration of SF6 gas generated in the
specimen collection booth was effectively reduced by the ventilation system. Additionally, the SF6 gas was not detected in the examination
room due to the maintenance of an appropriate differential pressure. |