Title Evaluation on Heat Exchange Effectiveness and System Energy Usage according to Occurrence of Cooling Coil Fouling
Authors 진산(San Jin) ; 장승민(Seungmin Jang) ; 박병용(Byeungyong Park) ; 조진균(Jinkyun Cho) ; 도성록(Sung Lok Do)
DOI https://doi.org/10.5659/JAIK.2023.39.5.141
Page pp.141-146
ISSN 2733-6247
Keywords Coil; Fouling; Effectiveness; HVAC system; Energy usage
Abstract A heating surface of a coil is exposed to various environments contaminated by various materials such as dust, scaling, and others over time. This phenomenon that contaminants attach and accumulate little by little on the heating surface of the coil is called fouling. Fouling involves contaminants of the inner and outer surfaces of the coil by adhering particulates and sediments. Fouling generates a thermal resistance layer on the coil, this layer decreases the heat exchange effectiveness of the coil. Eventually, this phenomenon leads to a reduction in performance and increases the energy usage of the HVAC system. Therefore, this study evaluated the heat exchange effectiveness and HVAC system energy usage to analyze the effect of the fouling on the HVAC system. To achieve this, a building energy simulation was conducted by assuming a situation in which fouling occurred. As a results, the heat exchange effectiveness decreased over time. The inner surface fouling had a greater effect on the decrease in effectiveness and the increase in energy usage than the outer surface fouling.