Title A Numerical Analysis for Determining Stable Operating Temperature Limits by Coolant Type in Single-Phase Immersion-Cooled Data Centers
Authors 조진균(Cho, Jinkyun)
DOI https://doi.org/10.5659/JAIK.2026.42.10.347
Page pp.347-356
ISSN 2733-6247
Keywords Immersion Cooling; Data Center; Dielectric Fluid; Junction Temperature; Computational Fluid Dynamics; Thermal Safety
Abstract High-density data centers driven by AI and HPC workloads are reaching rack power densities that exceed the limits of conventional air cooling, making single-phase immersion cooling a promising alternative. However, the stable operating range of such systems depends strongly on the dielectric fluid and the coolant supply temperature, which has not been systematically quantified. This study uses conjugate heat transfer CFD analysis to determine the safe operating temperature limits of a 50 kW immersion-cooled GPU server (80 H100-class GPUs at 625 W each; junction-temperature limit of 87°C) for three single-phase fluids, FC-40, mineral oil, and synthetic ester, at coolant inlet temperatures of 30, 40, and 50°C under a fixed 5°C inlet-to-outlet temperature difference. At inlet temperatures of 30°C and 40°C, all three fluids keep the maximum GPU junction temperature below the 87°C limit, whereas at 50°C only FC-40 remains within the limit (85.8°C); mineral oil (87.9°C) and synthetic ester (89.1°C) exceed it. The upper-to-lower junction-temperature gradient increases in the order FC-40 < mineral oil < synthetic ester, governed primarily by volumetric heat capacity, viscosity, and thermal diffusivity rather than by flow rate. The results indicate that the safe supply-temperature envelope is fluid-dependent: FC-40 offers the widest thermal margin but is subject to PFAS phase-out, while non-PFAS fluids remain safe only up to a 40°C supply temperature. These findings provide quantitative guidance for the cooling-system design and operation of high-density immersion-cooled data centers.