Title |
Defects Detection of the Underground Distribution Power Cables by Very Low Frequency Voltage Source |
Abstract |
This parer presents experimental results on the application of very low frequency(VLF) voltage to replace conventional DC test as an after laying test for underground distribution cables. We carried out several tests to prove defects detecting ability of VLF test on the 5m length real cables having knife-cut or needle type defects which is made in our Lab. Through this experiment we proved it is very difficult to initiate electrical tree from the defects inside of the cable insulation but once the electrical tree is initiated it grows very fast and VLF does not make new defects and expand the defect. Therefore VLF test equipment for quality inspection test of manufacture is mare effective than field application for underground distribution cables. |