Mobile QR Code QR CODE : Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

ISO Journal TitleJ Korean Inst. IIIum. Electr. Install. Eng.
Title A Detection Method of Resistive Leakage Current Flowing through ZnO Arrester Blocks
Authors Bok-Hee Lee ; Sung-Man Kang
Page pp.67-73
ISSN 1225-1135
Abstract This paper presents a developed measuring device of resistive leakage current and a fundamental discussion of deterioration diagnosis for Zinc Oxide(ZnO) arrester blocks. We have developed the leakage current detection device for ageing test and durability evaluation for ZnO arrester blocks. The resistive leakage current can be used as an indicator to discriminate whether the ZnO arrester blocks is in good state or in bad. The resistive leakage current measuring system with the compensation circuit was designed and fabricated. The sample tests for ZnO arrester blocks were investigated by observing the resistive leakage current together with fast Fourier transform analysis. The proposed monitoring systems for the resistive leakage current can effectively be used to investigate the electrophysical properties of ZnO arrester blocks in laboratory and to develop the techniques of forecasting the deterioration of ZnO arresters in electric power systems.