Mobile QR Code QR CODE : Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

ISO Journal TitleJ Korean Inst. IIIum. Electr. Install. Eng.
Title Compensate Voltage Drop for Autotransformer-Fed AC Electric Railroad System with Single-Phase STATCOM
Authors Hyun-soo Jung ; Seung-Hyuk Lee ; Jin-O Kim
Page pp.53-60
ISSN 1225-1135
Abstract This paper presents exact autotransformer-fed AC electric railroad system modeling using constant current mode, and single-phase STATCOM(Static Synchronous Compensator) which has an effect on electric railroad system. An AC electric railroad is rapidly changing single-phase feeding electric power. To avoid voltage fluctuation under single phase loads, electric power should be received from a large source. The system modeling theory is based on the solution of algebraic. The AC electric railroad load model is nonlinear. Therefore this paper is considered nonlinear load using PSCAD/EMTDC. And the proposed modeling method is considered the line self-impedances and mutual-impedances that techniques for the AC electric railroad system modeling analysis, and that single-phase STATCOM can reliably compensate the voltage drop. In the case study, the allowance range of feeding voltage is 22.5~27.5 kV, AT-fed AC electric railroad system circuit is analyzed by loop equation both normal and extension modes. The simulation objectives are to calculate the catenary and rail voltages with respect to ground, as the train moves along a section of line between two adjacent ATs. The results show that single-phase STATCOM can reduce the voltage drop in the feeding circuit and improve the power quality at AC electric railroad system by compensating the reactive power.