Title |
A Study on Lighting Energy Conservation in a Small Office Space with Daylight Dimming Control System |
Authors |
Han-Seong Kim ; Kang-Soo Kim |
Abstract |
This paper presents field measurements on daylighting and electric lighting with dimming controlled systems for a small office in Seoul, Korea. And the main purpose of this study is to provide the evaluation data of lighting energy performance when a dimming system is installed. For the performance evaluation, the mock-up room(3.6×7.2×2.6[m]) was used for the actual test. The results of this study were as follows; 1) The correlation between daylight illuminance at a workplane(Ed) and the photosensor signal(Sd) was an important factor affecting the performance of daylight responsive dimming system, 2) The mock-up office space gained a sufficient workplace illuminance of 579[lux] with the dimming control system 3) About 53[%] of monthly lighting energy could be saved using the dimming control system. |