Title |
EMC Performance Improvement of Distribution Automation Circuit-Breaker by Modified Installing Method of Control Cable |
Authors |
Oun-Seok Kim ; Jae-Chul Kim |
Abstract |
The goal of this paper is to improve EMC performance of circuit breaker. Circuit breaker and control cubicle are interconnected by multi control cable. Also many control cables are laid on each apparatus. These control cables are directly connected by electronic components. So control cables are very important to improve EMC performance of circuit breaker. This paper suggests installing a ground conductor in parallel(PGC) to control cables. Also this paper suggests using shielding cables as secondary cables of voltage transformer in circuit breakers, and grounding both ends of shielding. After applying suggested methods, we verified EMC performance of circuit breaker is improved. |