Mobile QR Code QR CODE : Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

Journal of the Korean Institute of Illuminating and Electrical Installation Engineers

ISO Journal TitleJ Korean Inst. IIIum. Electr. Install. Eng.
Title The Particle-Initiated Breakdown Characteristics on the Spacer Surface for SF6 GIS
Authors 김정달 ; 이세훈
Page pp.3-11
ISSN 1225-1135
Abstract The influence due to particle contaminated on spacer surface is remarkable in the decreasing of dielectric strength in SF6 GIS. In relation with this problem, We studied, AC flash-over voltage characteristics and breakdown mechanism are investigated under metallic and insulating particle initiated condition in SF6 gas by varying the particle position, particle shape with a plane-plane electrode. The main results are as follows ① Influence of the flash-over voltage decrease for particle position is lowest in mid gap and is highest in separated small gap on electrode. ② The metallic particle shape which results in the more reduced flash-over voltage, the FOV saturation moved in to the region of low pressure. ③ Insulating particle less than O.6[㎜] are not almost influenced by the flash-over Voltage.